124
ADV200 • Quick start up guide - Specification and installation
41
Watchdog
Condition:
may occur during functioning when the watchdog protection of the micro is acti-
vated; the alarm is inserted in the alarm list and alarm log. After this alarm:
- the drive automatically runs a reset
- motor control is not available.
XXXXH-X
The XXXXH-X code indicates the reason for the error: take note for examination
with the service centre.
Solution:
If the alarm was a consequence of a variation to the drive configuration (parameter
setting, installation of an option, downloading of a PLC application), remove it.
Switch the drive off and then switch it on again.
42
Trap error
Condition:
this condition can occur during operation when the trap micro protection is enabled;
the alarm is included in the list of alarms and alarm log. After this alarm:
- the drive automatically runs a reset
- motor control is not available.
XXXXH-X
The XXXXH-X code (SubHandler-Class) indicates the reason for the error: take note
for examination with the service centre.
Solution:
If the alarm was a consequence of a variation to the drive configuration (parameter
setting, installation of an option, downloading of a PLC application), remove it.
Switch the drive off and then switch it on again.
43
System error
Condition:
this condition can occur during operation when the operating system protection is
enabled; the alarm is included in the list of alarms and alarm log. After this alarm:
- the drive automatically runs a reset
- motor control is not available.
XXXXH-X
The XXXXH-X code (Error-Pid) indicates the reason for the error: take note for
examination with the service centre.
Solution:
If the alarm was a consequence of a variation to the drive configuration (parameter
setting, installation of an option, downloading of a PLC application), remove it.
Switch the drive off and then switch it on again.
44
User error
Condition:
this condition can occur during operation when the software protection is enabled;
the alarm is included in the list of alarms and alarm log. After this alarm:
- the drive automatically runs a reset
- motor control is not available.
XXXXH-X
The XXXXH-X (Error-Pid) code indicates the reason for the error: make a note of
this to discuss it with the service centre.
Solution:
If the alarm was a consequence of a variation to the drive configuration (parameter
setting, installation of an option, downloading of a PLC application), remove it.
Switch the drive off and then switch it on again.
45
Param error
Condition:
if an error occurs during the enabling of the parameter database saved in the Flash
memory; the alarm is included in the list of alarms and alarm log.
XXXXH-X
The code XXXXH-X indicates the IPA of the parameter that has been set outside
the range allowed when the database is enabled.
Solution:
Set the parameter causing the error to a value within the range and run
Save param-
eter
. Switch the drive off and then switch it back on again.
If the IPA of the parameter is not shown in the manual, contact the service centre.
46
Load default
Condition:
this can occur during loading of the parameter database saved in the Flash memory
it is normal if it appears in the following conditions: the first time the drive is switched on,
when a new version of the firmware is downloaded, when the regulation is installed on a new
size, when a new region is entered. If this message appears when the drive is already in use it
means there has been a problem in the parameter database saved in the Flash memory.
If this message is displayed the drive restores the default database, i.e. the one downloaded.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The saved database refers to a different size and not to the current size
0004H-4
The saved database refers to a different region and not to the current region
Solution:
Set the parameters to the desired value and run Save parameter