CTP24 (29.05.2019)
Manual de ususario
/ User’s Manual / Manuel d’utilisation
Pag.4/10
GECA S.r.l. - Via Enrico Fermi, 98 25064 GUSSAGO (BS) ITALY Tel. +39 030 3730218 - Fax +39 030 3730228
ADVERTENCIA
Configure los interruptores DIP
antes de alimentar el panel de control.
ADVERTENCIA:
CONFIGURE LA ESCALA COMPLETA CORRECTA PARA LOS MODELOS DE DETECTOR DE GAS INSTALADOS
.
U
N AJUSTE INCORRECTO DE LA ESCALA COMPLETA PUEDE IMPEDIR LA ACTIVACIÓN DE LA ALARMA
,
CON LA CONSECUENTE
SITUACIÓN DE PELIGRO
(
GAS INFLAMABLE
).
GECA
NO SERÁ RESPONSABLE DE LOS DAÑOS CAUSADOS POR UNA
SELECCIÓN
/
INSTALACIÓN
/
CONFIGURACIÓN INCORRECTA O POR LA FALTA DE MANTENIMIENTO DEL PRODUCTO.
La unidad de control
no necesita ajustes
después de su instalación.
La unidad de control,
una vez configurados los interruptores DIP, no necesitará ajustes adicionales
tras la
instalación.
Durante el
precalentamiento de los detectores
, que dura aproximadamente 60 segundos, los relés de alarma
permanecen inhibidos, mientras que el LED amarillo y el relé
FAULT
están activados.
En caso de
cortocircuito entre los cables de conexión y un detector
, el circuito de protección interrumpirá la
alimentación de corriente.
Tanto el relé
FAULT
como el LED amarillo se activarán. Apague la unidad
CTP23
, elimine
la causa del cortocircuito y vuelva a encender la unidad.
Si un detector no está instalado
,
para evitar la intervención automática del relé
FAULT
, se debe
deshabilitar
la
entrada correspondiente. (
Interruptor DIP SW1
).
VERIFICACIÓN DE FUNCIONAMIENTO
Verificaciones periódicas
:
recomendamos realizar pruebas de funcionamiento cada 6-12 meses.
En el caso de
detectores remotos, consulte el manual de usuario específico.
ATENCIÓN
: Este procedimiento debe realizarse con mucha atención y por parte de personal cualificado y
autorizado, ya iniciarlo hará que se activen las dos salidas (relés), lo que a su vez activará los dispositivos de
alarma conectados. La tecla
TEST
se deshabilita si una o más entradas son superiores a 10% LEL.
Comprobación de funcionamiento del instrumento
:
Pulse y mantenga pulsada la tecla
TEST
durante 5
segundos hasta que el procedimiento de prueba se inicie,
indicado en la pantalla
. Los 3 LEDs se encenderán y
los relés
FAULT, ALARM1 y ALARM2
se activarán. Transcurridos 5 segundos, la unidad volverá automáticamente al
funcionamiento normal
.
EN
DESCRIPTION
The
CTP24
is a control unit for heating plants, or environments to be protected from possible flammable gas leaks.
The unit can be connected up to 4 remote gas detectors. They can be configured, all with a full scale of 20% LEL, if
they are Catalytic (K) type or all with 100% LEL scale, if they are Pellistor type P.
The
CTP24
is for wall mounting and the protection code is IP65. It is mains powered at 110÷240VAC / 50÷60Hz but
can also be connected either to an external 24VDC power supply (e.g. p
ower supply unit with two 12V-7A/h buffer
batteries, our mod. PS180/24VDC
).
On the front plate there are, three LED that indicate the operating status, the
display, which shows
the gas concen-
tration detected by each remote detector and two
function keys (
TEST and RESET
).
The control unit has two alarm levels with sealed relay outputs (
ALARM1 and ALARM2
), with tension free changeover
contacts. Furthermore, it is also present another output relay (
FAULT
) in positive
safety for fault situations.
The con-
trol unit has two auxiliary inputs.
AUX1
is to connect NO contact devices such as a
manual Button. AUX2
is the con-
trol input for our
Manual NC Resetting Valve with positioning sensor
.
In Fig.1
a connection example with 4 remote gas detectors, siren, manual reset solenoid valve and manual button.
OPERATIONAL DESCRIPTION
Power on
: all times the control unit is powered, the display shows the name of the manufacturer, the model and the
firmware version (eg.
GECA srl / CTP24 v.1.00
).
Language
: Then, on the display, the choice of available languages (eg EN-EN-FR) appears, pressing the RESET
key will change the language, pressing the TEST key confirms the choice. If you do not make a choice within 10
seconds, the program continues automatically maintaining the last selected language.
WARNING
: the language choice, always appears at each power on, but after 10 seconds the program will automatically continue maintain-
ing the last selected language.
Info
: then, always appear in sequence 3 screens with configuration set reminders via the Dip-Switch: SCALE OF
MEASURE / ALARMS THRESHOLD / ENABLED DETECTORS. Then the program continues automatically.
Preheating
:
when the control unit is powered, the preheating phase begins; the display
shows
the 60 seconds
countdown and the yellow LED flashes.
Normal operating
:
at the end of the preheating, the display shows the value of the gas concentration and the sta-
tus of the remote detectors.
The
Green LED
lights up
to indicate the normal operation and the presence of power.
The Red LED (
ALARM
):
lights up flashing,
if the gas concentration exceeds
the 1
st
alarm threshold (configurable to
10 or 15% LEL)
and
within 5 seconds the
ALARM 1
relay will activate. This relay is normally used as a prealarm us-
ing a siren (
Our model SE301A when powered by 230VAC or the model SE301B when powered by 24V
DC
).
The display shows the channel, in alarm, alternately displaying the value and writing AL1.
The Red LED (
ALARM
):
lights up
if the gas concentration exceeds
the 2
nd
alarm threshold
(20% LEL); if the gas
persists, after 30 seconds, the
ALARM 2
relay will activate. It
is configurable in positive (
normally energized
) or nega-