Hint!
After excess pressure has occurred in the control top, the venting
screw (52) must be replaced in order to further guarantee the IP
protection class.
Fig.9:
Control Top with Cap
This venting screw (52) is a safety device that must be handled as such and must
not be covered. When fitting the control top note that the installation position of
the further venting screws (Ex) must never be pointing vertically upwards.
3.2.6
Reset Function / Activating Automatic Programming Mode
In order to change saved positions (e.g. after seal replacement), the saved
positions have to be deleted (reset). The reset button must be pressed for 3 – 7
sec. for this.
•
Reset function is possible live.
•
After the button has been pressed for 3 seconds, the reset is initiated and the
LED goes off.
•
The actual reset is carried out as soon as the button is released. This must
take place within 4-7 seconds of pressing.
•
If the reset switch is not released after 7 seconds, no reset takes place and
the previously learnt actuated and non-actuated positions are retained and/or
normal mode is resumed. It is irrelevant how long the reset switch is pressed.
•
The learning process starts automatically 1-2 seconds after reset
®
Red steady light for 1-2 seconds. The LED flashes red until the signal of the
non-actuated position is recorded.