5-96
T60 Transformer Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
•
SWITCH 1 OPEN:
This setting selects an operand that creates a programmable signal to operate a contact output to
open disconnect switch 1.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWITCH 1 CLOSE:
This setting selects an operand that creates a programmable signal to operate a contact output to
close disconnect switch 1.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWTCH 1
Φ
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 89/a status input to create a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the
SWITCH 1
Φ
B
and
SWITCH 1
Φ
C
settings select operands to
track phases B and C, respectively.
•
SWTCH 1
Φ
A/3P OPND:
This setting selects an operand, usually a contact input, that should be a normally-closed 89/
b status input to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available,
then an inverted 89/a status signal can be used.
•
SWITCH 1
Φ
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
Φ
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
Φ
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
Φ
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 Toperate
: This setting specifies the required interval to overcome transient disagreement between the 89/a
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic™ operand is asserted from alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the T60 is in “Programmed” mode and not in the local control mode.
NOTE
Содержание UR T60
Страница 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 492: ...8 18 T60 Transformer Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 510: ...9 18 T60 Transformer Protection System GE Multilin 9 6 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...