Consult with qualified personnel to ensure that
electrical requirements for the switch are met.
© 2015 General Electric Company. All rights reserved
.
88 |
=
GE Oil & Gas
The maximum voltage that can be applied to the digital switch outputs is 30 VDC. This is an open
circuit parameter (the digital switch is in the open state). Under open circuit conditions, the
switch current will be less than 0.200 mA.
The switch maximum current rating is 1 A. When the switch is ON, the typical switch voltage is
1 V. It is essential that the external circuit controls voltage such that the switch saturation voltage
is maintained.
When the switch is on (closed) the external voltage must be dropped across the load (Figure 30).
The load must be designed such that the current in
the circuit is
1 A at all times. Some 3rd party
devices, such as incandescent lamps or solenoids,
require surge and back EMI protection to limit
current to
1 A.
Figure 30
Simplified Switch Installation Drawing: Correct Configuration
CAUTION
CAUTION
SVI II AP Switch
Output:
1 V
with switch ON
External
Voltage
Source
LOAD
Load is designed to ensure that voltage across the switch is < 1 V.
Содержание SVI II AP
Страница 6: ...Page Left Blank Intentionally ...
Страница 10: ...This page intentionally left blank ...
Страница 58: ...This page intentionally left blank ...
Страница 84: ... 2015 General Electric Company All rights reserved 84 GE Oil Gas ...
Страница 85: ...Masoneilan SVI II AP Digital Positioner Quick Start Guide 85 2015 General Electric Company All rights reserved ...
Страница 90: ...This page intentionally left blank ...
Страница 91: ......