P50 Agile P253
6 Protection Functions
P253/EN M/C
6-15
t = T *
K
I
I
s
α
- 1
+ L
Where;
t: Operation time
K: Constant (see the table)
I: Measured current
Is: Current threshold setting
α: Constant (see the table)
L: ANSI/IEEE constant (zero for IEC curve)
T: Time multiplier setting (TMS) for IEC curves or Time dial setting (TD) for IEEE curves
Description
Standard
K
α
L
Define Time
DT
-
-
0
Standard Inverse
IEC
0.14
0.02
0
Standard Inverse(1.3sec)
---
0.06
0.02
0
Very Inverse
IEC
13.5
1
0
Extremely inverse
IEC
80
2
0
Long Time Inverse
UK
120
1
0
Moderate Inverse
IEEE
0.0515
0.02
0.114
Very Inverse
IEEE
19.61
2
0.491
Extremely Inverse
IEEE
28.2
2
0.1217
US Inverse
CO8
5.95
2
0.18
US Short Time Inverse
CO2
0.02394
0.02
0.01694
2.4.2
Principle of Protection Function Implementation
An energising quantity is a current input from a system current transformer or another quantity derived
from the current input. The energising quantities are extracted from the power system and presented
to the IED in the form of analogue signals. These analogue signals are then converted to digital
quantities where they can be processed by the IEDs internal processor.
In general, an energising quantity is compared with a threshold value, which may be settable or hard-
coded depending on the function. If the quantity exceeds (for overvalues) or falls short of (for
undervalues) the threshold, a signal is produced, which when gated with the various inhibit and
blocking functions becomes the Start signal for that protection function. This Start signal is generally
made available to Fixed Scheme logic for further processing. It is also passed through a timer function
to produce the Trip signal. The timer function may be an IDMT curve, or a Definite Time delay,
depending on the function. The timer can be configured by a range of settings to define such
parameters as the type of curve, The Time Multiplier Setting, the IDMT constants and Definite Time
delay.
In P253 there are several independent stages for each of the functions. All the stages (1, 2 and 3) can
be set for DT/IDMT timer function. If the DT time delay is set to '0', then the function is known to be
"instantaneous". In many instances the term “instantaneous protection” is used loosely to describe
Definite Time protection stages even when the stage may not theoretically be instantaneous.
Содержание P50 Agile P253
Страница 3: ...P50 Agile P253 1 Introduction P253 EN M C 1 1 INTRODUCTION CHAPTER 1 ...
Страница 4: ...1 Introduction P50 Agile P253 1 2 P253 EN M C ...
Страница 11: ...SAFETY INFORMATION CHAPTER 2 ...
Страница 12: ...Safety Information Pxxx 2 ...
Страница 23: ...P50 Agile P253 3 Hardware Design P253 EN M C 3 1 HARDWARE DESIGN CHAPTER 3 ...
Страница 24: ...3 Hardware Design P50 Agile P253253 3 2 P253 EN M C ...
Страница 28: ...3 Hardware Design P50 Agile P253253 3 6 P253 EN M C E00276 Figure 2 Hardware design overview ...
Страница 32: ...3 Hardware Design P50 Agile P253253 3 10 P253 EN M C ...
Страница 33: ...P50 Agile P253 4 Front Panel P253 EN M C 4 1 FRONT PANEL CHAPTER 4 ...
Страница 34: ...4 Front Panel P50 Agile P253 4 2 P253 EN M C ...
Страница 39: ...P50 Agile P253 4 Front Panel P253 EN M C 4 7 Figure 2 USB port ...
Страница 40: ...4 Front Panel P50 Agile P253 4 8 P253 EN M C ...
Страница 41: ...P50 Agile P253 5 Configuration P253 EN M C 5 1 CONFIGURATION CHAPTER 5 ...
Страница 42: ...5 Configuration P50 Agile P253 5 2 P253 EN M C ...
Страница 154: ...5 Configuration P50 Agile P253 5 114 P253 EN M C ...
Страница 155: ...P50 Agile P253 6 Protection Functions P253 EN M C 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Страница 156: ...6 Protection Functions P50 Agile P253 6 2 P253 EN M C ...
Страница 181: ...P50 Agile P253 7 Protection Parameter Settings P253 EN M C 7 1 PROTECTION PARAMETER SETTINGS CHAPTER 7 ...
Страница 182: ...7 Protection Parameter Settings P50 Agile P253 7 2 P253 EN M C ...
Страница 203: ...P50 Agile P253 8 Monitoring Control P253 EN M C 8 1 MONITORING CONTROL CHAPTER 8 ...
Страница 204: ...8 Monitoring Control P50 Agile P253 8 2 P253 EN M C ...
Страница 222: ...8 Monitoring Control P50 Agile P253 8 20 P253 EN M C ...
Страница 223: ...P50 Agile P253 9 SCADA Communications P253 EN M C 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Страница 224: ...9 SCADA Communications P50 Agile P253 9 2 P253 EN M C ...
Страница 249: ...P50 Agile P253 10 Installation P253 EN M C 10 1 INSTALLATION CHAPTER 10 ...
Страница 250: ...10 Installation P50 Agile P253 10 2 P253 EN M C ...
Страница 259: ...P50 Agile P253 11 Commissioning Instructions P253 EN M C 11 1 COMMISSIONING INSTRUCTIONS CHAPTER 11 ...
Страница 260: ...11 Commissioning Instructions P50 Agile P253 11 2 P253 EN M C ...
Страница 270: ...11 Commissioning Instructions P50 Agile P253 11 12 P253 EN M C ...
Страница 271: ...P50 Agile P253 12 Maintenance and Troubleshooting P253 EN M C 12 1 MAINTENANCE AND TROUBLESHOOTING CHAPTER 12 ...
Страница 272: ...12 Maintenance and Troubleshooting P50 Agile P253 12 2 P253 EN M C ...
Страница 281: ...P50 Agile P253 13 Technical Specifications P253 EN M C 13 1 TECHNICAL SPECIFICATIONS CHAPTER 13 ...
Страница 282: ...13 Technical Specifications P50 Agile P253 13 2 P253 EN M C ...
Страница 292: ...13 Technical Specifications P50 Agile P253 13 12 P253 EN M C ...
Страница 293: ...P50 Agile P253 14 Wiring Diagrams P253 EN M C 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Страница 294: ...14 Wiring Diagrams P50 Agile P253 14 2 P253 EN M C ...
Страница 296: ...14 Wiring Diagrams P50 Agile P253 14 4 P253 EN M C 2 WIRING DIAGRAM Figure 1 P253 wiring diagram ...
Страница 297: ......