7 Protection Parameter Settings
P50 Agile P253
7-6
P253/EN M/C
Sr. No
Parameter
Defaults setting
Setting/Ranges
11.
DST End Day
Sunday
Sunday/Monday/Tuesday/Wednesday/Thursday/Friday/Saturday
Setting to specify the day of the week in which daylight saving time adjustment ends
12.
DST End Month
October
January/February/March/April/May/June/July/August/September
/October/November/December
Setting to specify the month in which daylight saving time adjustment ends
13.
DST End Mins
60 Mins
0 to 1425 mins step of 15mins.
Setting to specify the time of day in which daylight saving time adjustment ends. This is set relative to 00:00 hrs on the selected day when
time adjustment is to end
14.
RP Time Zone
Local
UTC/Local
Setting for the rear port 1 interface to specify if time synchronization received will be local or universal time co-ordinated.
15.
SET Hours
11 *
0 to 23 Hrs step of 1.
Hour setting needed when relay is not connected to SCADA system
16.
SET Minutes
35 *
0 to 59 Mins in step of 1.
Minutes setting needed when relay is not connected to SCADA system
17.
SET Seconds
54 *
0 to 59 Sec. in step of 1.
Seconds setting needed when relay is not connected to SCADA system
18.
SET Date
28 *
1 to 31 Days step of 1.
Date setting needed when relay is not connected to SCADA system
19.
SET Month
10 *
1 to 12 Months step of 1.
Month setting needed when relay is not connected to SCADA system
20.
SET Year
14 *
0 to 99 Years step of 1.
Year setting needed when relay is not connected to SCADA system
Note:* The relay displays the current Date/Time set in the relay.
2.4
CONFIGURATION Settings
Sr. No
Parameter
Defaults setting
Setting/Ranges
1.
Password
0000
0000 to zzzz
This setting specifies to enter the set password
2.
Restore Defaults
No Operation
No Operation/All Settings/Setting Group 1/Setting
Group 2
This setting restores the chosen setting groups to factory default values.
To restore the default values to any Group, set the ‘restore defaults’ cell to the relevant Group number. Alternatively, it is possible to set
the ‘restore defaults’ cell to ‘all settings’ to restore the default values to all of the IED’s settings, not just the Group settings.
The default settings will be placed in Flash and will only be used by the IED after they have been confirmed by the user.
Note:
Restoring defaults to all settings includes the rear communication port settings, which
may result in communication via the rear port being disrupted if the new (default)
settings do not match those of the master station.
3.
Active Settings
Group 1
Group 1/Group 2
This setting selects the active settings group.
4.
Copy From
Group 1
Group 1/Group 2
This setting allows settings to be copied from a selected setting group.
5.
Copy To
No Operation
No Operation/Group 1/Group 2
Содержание P50 Agile P253
Страница 3: ...P50 Agile P253 1 Introduction P253 EN M C 1 1 INTRODUCTION CHAPTER 1 ...
Страница 4: ...1 Introduction P50 Agile P253 1 2 P253 EN M C ...
Страница 11: ...SAFETY INFORMATION CHAPTER 2 ...
Страница 12: ...Safety Information Pxxx 2 ...
Страница 23: ...P50 Agile P253 3 Hardware Design P253 EN M C 3 1 HARDWARE DESIGN CHAPTER 3 ...
Страница 24: ...3 Hardware Design P50 Agile P253253 3 2 P253 EN M C ...
Страница 28: ...3 Hardware Design P50 Agile P253253 3 6 P253 EN M C E00276 Figure 2 Hardware design overview ...
Страница 32: ...3 Hardware Design P50 Agile P253253 3 10 P253 EN M C ...
Страница 33: ...P50 Agile P253 4 Front Panel P253 EN M C 4 1 FRONT PANEL CHAPTER 4 ...
Страница 34: ...4 Front Panel P50 Agile P253 4 2 P253 EN M C ...
Страница 39: ...P50 Agile P253 4 Front Panel P253 EN M C 4 7 Figure 2 USB port ...
Страница 40: ...4 Front Panel P50 Agile P253 4 8 P253 EN M C ...
Страница 41: ...P50 Agile P253 5 Configuration P253 EN M C 5 1 CONFIGURATION CHAPTER 5 ...
Страница 42: ...5 Configuration P50 Agile P253 5 2 P253 EN M C ...
Страница 154: ...5 Configuration P50 Agile P253 5 114 P253 EN M C ...
Страница 155: ...P50 Agile P253 6 Protection Functions P253 EN M C 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Страница 156: ...6 Protection Functions P50 Agile P253 6 2 P253 EN M C ...
Страница 181: ...P50 Agile P253 7 Protection Parameter Settings P253 EN M C 7 1 PROTECTION PARAMETER SETTINGS CHAPTER 7 ...
Страница 182: ...7 Protection Parameter Settings P50 Agile P253 7 2 P253 EN M C ...
Страница 203: ...P50 Agile P253 8 Monitoring Control P253 EN M C 8 1 MONITORING CONTROL CHAPTER 8 ...
Страница 204: ...8 Monitoring Control P50 Agile P253 8 2 P253 EN M C ...
Страница 222: ...8 Monitoring Control P50 Agile P253 8 20 P253 EN M C ...
Страница 223: ...P50 Agile P253 9 SCADA Communications P253 EN M C 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Страница 224: ...9 SCADA Communications P50 Agile P253 9 2 P253 EN M C ...
Страница 249: ...P50 Agile P253 10 Installation P253 EN M C 10 1 INSTALLATION CHAPTER 10 ...
Страница 250: ...10 Installation P50 Agile P253 10 2 P253 EN M C ...
Страница 259: ...P50 Agile P253 11 Commissioning Instructions P253 EN M C 11 1 COMMISSIONING INSTRUCTIONS CHAPTER 11 ...
Страница 260: ...11 Commissioning Instructions P50 Agile P253 11 2 P253 EN M C ...
Страница 270: ...11 Commissioning Instructions P50 Agile P253 11 12 P253 EN M C ...
Страница 271: ...P50 Agile P253 12 Maintenance and Troubleshooting P253 EN M C 12 1 MAINTENANCE AND TROUBLESHOOTING CHAPTER 12 ...
Страница 272: ...12 Maintenance and Troubleshooting P50 Agile P253 12 2 P253 EN M C ...
Страница 281: ...P50 Agile P253 13 Technical Specifications P253 EN M C 13 1 TECHNICAL SPECIFICATIONS CHAPTER 13 ...
Страница 282: ...13 Technical Specifications P50 Agile P253 13 2 P253 EN M C ...
Страница 292: ...13 Technical Specifications P50 Agile P253 13 12 P253 EN M C ...
Страница 293: ...P50 Agile P253 14 Wiring Diagrams P253 EN M C 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Страница 294: ...14 Wiring Diagrams P50 Agile P253 14 2 P253 EN M C ...
Страница 296: ...14 Wiring Diagrams P50 Agile P253 14 4 P253 EN M C 2 WIRING DIAGRAM Figure 1 P253 wiring diagram ...
Страница 297: ......