6 Protection Functions
P50 Agile P253
6-20
P253/EN M/C
Each column contains an identical set of elements, whereby the
EARTH FAULT 1
(IN1) column is
used for earth fault current that is measured directly from the system, whilst the
EARTH FAULT 2
(IN2) column contains cells, which operate from a residual current quantity that is derived internally
from the summation of the three-phase currents.
The product provides three stages of Earth Fault protection with independent time delay
characteristics, for each EARTH FAULT column.
Stages 1, 2 and 3 provide a choice of operate and reset characteristics, where you can select
between:
•
A range of standard IDMT (Inverse Definite Minimum Time) curves
•
DT (Definite Time)
For the IN1 column, this is achieved using the cells:
•
IN1>(n) Function
for the overcurrent operate characteristics
•
IN1>(n) Reset Char
for the overcurrent reset characteristic
For the IN2 column, this is achieved using the cells:
•
IN2>(n) Function
for the overcurrent operate characteristics
•
IN2>(n) Reset Char
for the overcurrent reset characteristic
where (n) is the number of the stage.
Stages 1, 2 and 3 provide a Timer Hold facility. This is configured using the cells
IN1>(n) tRESET
for
Earth Fault 1 and
IN2>(n) tRESET
for Earth Fault 2.
The fact that both EF1 and EF2 elements may be enabled at the same time leads to a number of
application advantages.
2.7.2
Earth Fault Protection Logic
The Earth Fault current is compared with a set threshold (
IN1>(n) Current Set
) for each stage. If it
exceeds this threshold a Start signal is triggered, provided there are no blocks.
Earth Fault protection can follow the same IDMT characteristics as described in the Overcurrent
Protection Principles section. Please refer to this section for details of IDMT characteristics.
The description also applies to the Earth Fault 2 element (IN2).
The Earth Fault protection trip signal can be blocked by:
•
The Second Harmonic blocking function which is for all three phases. The blocking of Earth
Fault 1 is activated by setting the
IN1>(n) 2H Blocking
cell to ‘Enabled’ and blocking of Earth
Fault 2 is activated by setting the
IN2>(n) 2H Blocking
cell to ‘Enabled’, where (n) is the
number of the stage.
•
User defined blocking logic using ‘IO Mask’ functionality.
2.8
Sensitive Earth Fault Protection
With some earth faults the fault current flowing to earth is limited by either intentional resistance (as is
the case with some HV systems) or unintentional resistance. For example, in very dry conditions and
where the substrate is high resistance, such as sand or rock.
To provide protection in such cases it is necessary to provide an earth fault protection system with a
setting that is considerably lower than for normal line protection. Such sensitivity cannot be provided
with conventional CTs, therefore SEF would normally be fed from a core balance current transformer
(CBCT) mounted around the three phases of the feeder cable. Also a special measurement class SEF
transformer should be used in the IED.
With SEF protection, settings as low as 0.2% can be used.
Содержание P50 Agile P253
Страница 3: ...P50 Agile P253 1 Introduction P253 EN M C 1 1 INTRODUCTION CHAPTER 1 ...
Страница 4: ...1 Introduction P50 Agile P253 1 2 P253 EN M C ...
Страница 11: ...SAFETY INFORMATION CHAPTER 2 ...
Страница 12: ...Safety Information Pxxx 2 ...
Страница 23: ...P50 Agile P253 3 Hardware Design P253 EN M C 3 1 HARDWARE DESIGN CHAPTER 3 ...
Страница 24: ...3 Hardware Design P50 Agile P253253 3 2 P253 EN M C ...
Страница 28: ...3 Hardware Design P50 Agile P253253 3 6 P253 EN M C E00276 Figure 2 Hardware design overview ...
Страница 32: ...3 Hardware Design P50 Agile P253253 3 10 P253 EN M C ...
Страница 33: ...P50 Agile P253 4 Front Panel P253 EN M C 4 1 FRONT PANEL CHAPTER 4 ...
Страница 34: ...4 Front Panel P50 Agile P253 4 2 P253 EN M C ...
Страница 39: ...P50 Agile P253 4 Front Panel P253 EN M C 4 7 Figure 2 USB port ...
Страница 40: ...4 Front Panel P50 Agile P253 4 8 P253 EN M C ...
Страница 41: ...P50 Agile P253 5 Configuration P253 EN M C 5 1 CONFIGURATION CHAPTER 5 ...
Страница 42: ...5 Configuration P50 Agile P253 5 2 P253 EN M C ...
Страница 154: ...5 Configuration P50 Agile P253 5 114 P253 EN M C ...
Страница 155: ...P50 Agile P253 6 Protection Functions P253 EN M C 6 1 PROTECTION FUNCTIONS CHAPTER 6 ...
Страница 156: ...6 Protection Functions P50 Agile P253 6 2 P253 EN M C ...
Страница 181: ...P50 Agile P253 7 Protection Parameter Settings P253 EN M C 7 1 PROTECTION PARAMETER SETTINGS CHAPTER 7 ...
Страница 182: ...7 Protection Parameter Settings P50 Agile P253 7 2 P253 EN M C ...
Страница 203: ...P50 Agile P253 8 Monitoring Control P253 EN M C 8 1 MONITORING CONTROL CHAPTER 8 ...
Страница 204: ...8 Monitoring Control P50 Agile P253 8 2 P253 EN M C ...
Страница 222: ...8 Monitoring Control P50 Agile P253 8 20 P253 EN M C ...
Страница 223: ...P50 Agile P253 9 SCADA Communications P253 EN M C 9 1 SCADA COMMUNICATIONS CHAPTER 9 ...
Страница 224: ...9 SCADA Communications P50 Agile P253 9 2 P253 EN M C ...
Страница 249: ...P50 Agile P253 10 Installation P253 EN M C 10 1 INSTALLATION CHAPTER 10 ...
Страница 250: ...10 Installation P50 Agile P253 10 2 P253 EN M C ...
Страница 259: ...P50 Agile P253 11 Commissioning Instructions P253 EN M C 11 1 COMMISSIONING INSTRUCTIONS CHAPTER 11 ...
Страница 260: ...11 Commissioning Instructions P50 Agile P253 11 2 P253 EN M C ...
Страница 270: ...11 Commissioning Instructions P50 Agile P253 11 12 P253 EN M C ...
Страница 271: ...P50 Agile P253 12 Maintenance and Troubleshooting P253 EN M C 12 1 MAINTENANCE AND TROUBLESHOOTING CHAPTER 12 ...
Страница 272: ...12 Maintenance and Troubleshooting P50 Agile P253 12 2 P253 EN M C ...
Страница 281: ...P50 Agile P253 13 Technical Specifications P253 EN M C 13 1 TECHNICAL SPECIFICATIONS CHAPTER 13 ...
Страница 282: ...13 Technical Specifications P50 Agile P253 13 2 P253 EN M C ...
Страница 292: ...13 Technical Specifications P50 Agile P253 13 12 P253 EN M C ...
Страница 293: ...P50 Agile P253 14 Wiring Diagrams P253 EN M C 14 1 WIRING DIAGRAMS CHAPTER 14 ...
Страница 294: ...14 Wiring Diagrams P50 Agile P253 14 2 P253 EN M C ...
Страница 296: ...14 Wiring Diagrams P50 Agile P253 14 4 P253 EN M C 2 WIRING DIAGRAM Figure 1 P253 wiring diagram ...
Страница 297: ......