124
GE INFORMATION
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
CHAPTER 10: INTRODUCING THE D400 CONFIGURATION
Timestamps and time zones on your D400
All timestamps on the D400 are stored in UTC (coordinated universal time). Table 28
explains how time zones are handled by various components of the D400 and how this
behavior can be configured.
Table 28: Time configuration
NOTE
The IEC 60870-5-103 Client and IEC 60870-5-101+104 client applications are not available
in this release.
NOTE
The IEC 60870-5-101+104 application uses a slightly different concept for local to UTC time
conversion in order to be consistent with the D2x product family. If the master is in a
different time zone, you should set the Time Mode field to Set local/use local time. When
the master time synchronizes the application, the application calculates the difference
between the internal D400 UTC clock and the master's time. The application then applies
this difference to the UTC timestamps it reports to the master. In effect, it automatically
calculates the time offset.
Component
Time zone handling
Configuration Method
D400
system clock
For all of the time zone features
described in this document to
work properly, the
D400
hardware clock must be set to
UTC using the appropriate
D400
BIOS setting.
Configured using the
d400cfg
utility. >
“Set System Clock” on page 146
Device and master station
internal clocks
Can be set to local time or UTC,
as desired.
Refer to the user documentation
provided with the device or master
station. If the device’s clock is offset
from UTC, the same offset should be
configured in the corresponding client
map file (see below).
Time-stamped data
communicated to the
D400
The timestamp is converted to
UTC from the configured offset
or is left unmodified if no offset
is configured.
Defined by the Time Offset field in the
client map files. Refer to
D400
Online
Help > DNP3 Client topic, IEC 60870-5-
103 with
D400
Master Application
topic, or IEC 60870-5-101+104 with
D400
Master Application topic, See
notes below table).
Time-stamped data
communicated from the
D400
The timestamp is converted
from UTC to the configured
offset or is left at UTC if no offset
is configured.
Defined by the
Time Offset
field. See
the
D400
Online Help > DNP Server
topic.
Local console (including
local HMI) and command
line via TELNET/SSH
All time-stamped data is shown
to you using the configured
D400
time zone setting.
Configured using the
d400cfg
utility. >
D400
web-based HMI
All time-stamped data is shown
to you using the time zone
configured on the remote PC.
Refer to the user documentation
provided with the operating system
installed on the remote PC.
Содержание Multilin D400
Страница 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Страница 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Страница 80: ...80 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 4 CONNECTING TO DEVICES AND NETWORKS ...
Страница 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Страница 104: ...104 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 7 SETTING UP THE D400 FOR REDUNDANCY ...
Страница 118: ...118 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 9 ABOUT THE D400 APPLICATIONS ...
Страница 126: ...126 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 10 INTRODUCING THE D400 CONFIGURATION ...
Страница 158: ...158 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 12 USING THE D400 LOCAL CONFIGURATION UTILITY ...