6. ACCEPTANCE TESTS
GEK-106271
MIV Digital Multifunctional Protective Relay
53
SYNCHRONISM CHECK UNIT:
89 OPEN, Compare V1 with V2:
•
Remove auxiliary voltage from terminal PI1 (89 open).
•
Apply 60 Vac at 60 Hz to V1 and V2 with an angle difference of 0º between both voltages.
•
Change the following settings and check that contacts SP1, SP2, SP3 and SP4 close.
GENERAL SETTINGS
FREQUENCY
60 Hz
25 SETTINGS FOR 521
79/ DL-DB
Not permitted
79/ LL-DB
Not permitted
79/ DL-LB
Not permitted
79/ SYNCHECK
permitted
CLOSE/ DL-DB
Not permitted
CLOSE/ LL-DB
Not permitted
CLOSE/ DL-LB
Not permitted
CLOSE/ SYNCHECK
permitted
25 SETTINGS FOR 520
79/ DL-DB
Not permitted
79/ LL-DB
Not permitted
79/ DL-LB
Not permitted
79/ SYNCHECK
permitted
CLOSE/ DL-DB
Not permitted
CLOSE/ LL-DB
Not permitted
CLOSE/ DL-LB
Not permitted
CLOSE/ SYNCHECK
permitted
•
Increase voltage V1 and check that for 70 Vac, contacts SP1, SP2, SP3 and SP4 open.
•
Decrease V1 voltage to 60 Vac.
•
Change V1 angle with respect to V2, and check that when reaching 10º , contacts SP1, SP2, SP3 and SP4
open.
89 CLOSED, Compare V1 with V4:
•
Apply auxiliary voltage only to PI1 (89 closed).
•
Apply 60 Vac at 60 Hz to V1, V2 and V4 with an angle difference of 0º between V1-V4 and V2-V4, and check
that contacts SP1, SP2, SP3 and SP4 close.
•
Increase V4 and check that when reaching 70 Vac, contacts SP1, SP2, SP3 and SP4 open.
•
Decrease V4 to 60 Vac.
•
Change V4 angle with respect to V1 and V2, and check that when reaching 10º, contacts SP1, SP2, SP3 and
SP4 open.
6.16. IRIG-B
•
Synchronise the relay with the date and time of the PC that is being used to communicate with the unit.
•
Check that the relay and the PC show the same time.
•
Place in the IRIG-B receiver a date/time completely different from the current time, which is on the PC.
•
Connect the IRIG-B receiver to the relay.
•
Check that the relay and the IRIG-B receiver show the same date/time.
Содержание MOV 2000
Страница 3: ......
Страница 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 9: ...1 GENERAL DESCRIPTION AND APPLICATION 6 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 72: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 69 FIGURES FIGURES FIGURES FIGURES ...
Страница 73: ...FIGURES 70 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 1 PANEL MOUNTING DIAGRAM 226B6086H10 ...
Страница 74: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 71 FIGURE 2 FRONT VIEW 226B7412H9 ...
Страница 75: ...FIGURES 72 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 3 EXTERNAL CONNECTIONS 189C4129 H1 ...
Страница 77: ...FIGURES 74 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 6 REAR VIEW 226B7412H10 ...
Страница 78: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 75 FIGURE 7 DIMENSIONS DIAGRAM 226B6086H10 ...