6. ACCEPTANCE TESTS
48
MIV Digital Multifunctional Protective Relay
GEK-106271
FUNCTION F:
89 OPEN:
•
Apply auxiliary voltage only to PI2 (89 open)
•
Apply Vac voltage corresponding to half the voltage presence setting to V1.
•
Increase V1 and check that terminal SP9 is activated for 100% and deactivated for 96% of the voltage
presence setting.
89 CLOSED, VOLTAGE IN PHASE A:
•
Apply auxiliary voltage only to PI1(89 closed)
•
Apply Vac voltage corresponding to half the voltage presence setting to V3.
•
Increase V3 and check that terminal SP9 is activated for 100% and deactivated for 96% of the voltage
presence setting.
VOLTAGE IN PHASE B:
•
Apply Vac voltage corresponding to half the voltage presence setting to V4.
•
Increase V4 and check that terminal SP9 is activated for 100% and deactivated for 96% of the voltage
presence setting.
VOLTAGE IN PHASE C:
•
Apply Vac voltage corresponding to half the voltage presence setting to V5.
•
Increase V5 and check that terminal SP9 is activated for 100% and deactivated for 96% of the voltage
presence setting.
FUNCTION J:
89 UNDETERMINED:
•
Apply auxiliary voltage to PI1 and PI2 (89 undetermined)
•
Apply Vac voltage corresponding to half the voltage presence setting to V1.
•
Increase V1 and check that terminal SP21 is activated for 100% and deactivated for 96% of the voltage
presence setting.
89 OPEN:
•
Apply auxiliary voltage only to PI2 (89 open)
•
Apply Vac voltage corresponding to half the voltage presence setting to V2.
•
Increase V2 and check that terminal SP21 is activated for 100% and deactivated for 96% of the voltage
presence setting.
89 CLOSED, VOLTAGE IN PHASE A:
•
Apply auxiliary voltage only to PI1 (89 closed)
•
Apply Vac voltage corresponding to half the voltage presence setting to V3.
•
Increase V3 and check that terminal SP21 is activated for 100% and deactivated for 96% of the voltage
presence setting.
VOLTAGE IN PHASE B:
•
Apply Vac voltage corresponding to half the voltage presence setting to V4.
•
Increase V4 and check that terminal SP21 is activated for 100% and deactivated for 96% of the voltage
presence setting.
Содержание MOV 2000
Страница 3: ......
Страница 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 9: ...1 GENERAL DESCRIPTION AND APPLICATION 6 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 72: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 69 FIGURES FIGURES FIGURES FIGURES ...
Страница 73: ...FIGURES 70 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 1 PANEL MOUNTING DIAGRAM 226B6086H10 ...
Страница 74: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 71 FIGURE 2 FRONT VIEW 226B7412H9 ...
Страница 75: ...FIGURES 72 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 3 EXTERNAL CONNECTIONS 189C4129 H1 ...
Страница 77: ...FIGURES 74 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 6 REAR VIEW 226B7412H10 ...
Страница 78: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 75 FIGURE 7 DIMENSIONS DIAGRAM 226B6086H10 ...