6. ACCEPTANCE TESTS
44
MIV Digital Multifunctional Protective Relay
GEK-106271
UNDERVOLTAGE TIMER
0,2s
UNDERVOLTAGE’ TIMER
0,2s
PROTECTION INPUTS
Protection input 1
Input_89L_A
Protection input 2
Input _89L_B
PROTECTION OUTPUTS
Protection output 1
FUNCTION A
Protection output 2
FUNCTION A'
FUNCTION A’:
89 OPEN
•
Apply auxiliary voltage through terminal PI2 (89 OPEN)
•
Apply Vac voltage corresponding to half the undervoltage setting in V3, V4 and V5.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V1.
•
Decrease V1 and check that terminal SP2 is activated for 100%, and deactivated for 104% of the undervoltage
setting.
89 CLOSED
•
Apply auxiliary voltage only through the input terminal PI1 (89 closed).
•
Apply Vac voltage corresponding to half the undervoltage setting in V1.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V3, V4 and V5.
•
Decrease V3, V4 and V5, and check that terminal SP2 is activated for 100%, and deactivated for 104% of the
undervoltage setting.
FUNCTION A:
89 OPEN
•
Apply auxiliary voltage through terminal PI2 (89 OPEN)
•
Apply Vac voltage corresponding to half the undervoltage setting in V1.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V2.
•
Decrease V2 and check that terminal SP1 is activated for 100%, and deactivated for 104% of the undervoltage
setting.
•
Apply auxiliary voltage through terminal PI2 (89 OPEN)
•
Apply Vac voltage corresponding to half the undervoltage setting in V2.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V1.
•
Decrease V1 and check that terminal SP1 is activated for 100%, and deactivated for 104% of the undervoltage
setting.
89 CLOSED
•
Apply auxiliary voltage only through the input terminal PI1 (89 closed).
•
Apply Vac voltage corresponding to half the undervoltage setting in V1.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V3, V4 and V5.
•
Decrease V3, V4 and V5 simultaneously, and check that terminal SP1 is activated for 100%, and deactivated
for 104% of the undervoltage setting.
•
Apply Vac voltage corresponding to half the undervoltage setting in V3, V4 and V5.
•
Apply Vac voltage corresponding to twice the undervoltage setting in V1.
•
Decrease V1, and check that terminal SP1 is activated for 100%, and deactivated for 104% of the
undervoltage setting.
Содержание MOV 2000
Страница 3: ......
Страница 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 9: ...1 GENERAL DESCRIPTION AND APPLICATION 6 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 72: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 69 FIGURES FIGURES FIGURES FIGURES ...
Страница 73: ...FIGURES 70 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 1 PANEL MOUNTING DIAGRAM 226B6086H10 ...
Страница 74: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 71 FIGURE 2 FRONT VIEW 226B7412H9 ...
Страница 75: ...FIGURES 72 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 3 EXTERNAL CONNECTIONS 189C4129 H1 ...
Страница 77: ...FIGURES 74 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 6 REAR VIEW 226B7412H10 ...
Страница 78: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 75 FIGURE 7 DIMENSIONS DIAGRAM 226B6086H10 ...