2. OPERATION PRINCIPLES
GEK-106271
MIV Digital Multifunctional Protective Relay
11
Table 1. Default LED configuration
COLUMN
LED Nº
LEFT
LED Nº
RIGHT
1
Function A (with memory)
9
Function H
2
Function A’ (with memory)
10
Function I
3
Function B
11
Function J
4
Function C
12
521 Instantaneous synchronism
5
Function D
13
520 Instantaneous synchronism
6
Function E
14
7
Function F
15
8
Function G
16
Local communication mode (blinking)
2.2.4. SELF TEST OF THE UNIT.
The MOV system incorporates, thanks to its digital technology, self-test functions that guarantee its correct
operation, and will disable the unit in case of internal orders.
These self-tests are performed both during start-up and normal operation. Tests are carried out on the internal
power supply, program memory (ROM), working memory (RAM), oscillography memory (RAM) and the settings
and calibration memory (EEPROM).
Additionally, a hardware test is included for the signalling LEDs. All of them will light up when pressing the
TARGET RESET button. If this button is pressed for more than one second, the memorised indicators will be
deleted.
2.3. ANALYSIS FUNCTIONS
The MOV system includes event recording and oscillography with time resolution of 1 millisecond. In order
to maintain the integrity of date and time, as well as the oscillography record, there is a capacitor backup for the
internal high-resolution clock and the oscillography memory, with capacity for storing the information during at
least 24 hours after a power supply breakdown.
2.3.1. EVENT RECORDER
The MOV keeps a record of the last 165 events, including date and time (with 1 ms resolution), event type,
current and voltage values when the event occurred, and unit status information.
This record is stored in a non volatile memory and is maintained event without power supply.
The following table shows the possible causes for an event:
Table 2. Causes for events
Index
Status
0.0
Program start-up
0.1
Settings change
0.2
Counters writing
0.5
W/o timers
0.6
Out of service
Содержание MOV 2000
Страница 3: ......
Страница 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 9: ...1 GENERAL DESCRIPTION AND APPLICATION 6 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 72: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 69 FIGURES FIGURES FIGURES FIGURES ...
Страница 73: ...FIGURES 70 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 1 PANEL MOUNTING DIAGRAM 226B6086H10 ...
Страница 74: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 71 FIGURE 2 FRONT VIEW 226B7412H9 ...
Страница 75: ...FIGURES 72 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 3 EXTERNAL CONNECTIONS 189C4129 H1 ...
Страница 77: ...FIGURES 74 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 6 REAR VIEW 226B7412H10 ...
Страница 78: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 75 FIGURE 7 DIMENSIONS DIAGRAM 226B6086H10 ...