6. ACCEPTANCE TESTS
GEK-106271
MIV Digital Multifunctional Protective Relay
39
6.
6.
6.
6.
ACCEPTANCE TESTS
ACCEPTANCE TESTS
ACCEPTANCE TESTS
ACCEPTANCE TESTS
There follows a list of tests which can be used to check that the unit is fully operational. For a more limited test for
the reception of units we recommend carrying out only the tests listed in sections: 6.2, 6.5, 6.6, 6.7 and 6.9.
6.1. CONNECTIONS AND NECESSARY EQUIPMENT
Necessary equipment:
•
Up to 5 AC voltage power supplies
•
One DC voltage power supply
•
One chronometer
•
One multimeter
Connect the relay as indicated in the external connections diagram, Figure 3 (189C4129F1).
Depending on each test, VAC power supplies shall be connected according to the wiring diagram.
For safety reasons, the relay shall be grounded.
Apply power always through terminals A10 and B10 at the rated voltage indicated on the front plate.
For simulating the external contacts closing (inputs to MOV unit) we will use jumpers and switches.
6.2. VISUAL INSPECTION
Check that the relay has not suffered any kind of damage due to transportation and handling.
Check that all the screws are sufficiently tight and that the terminal strips have not been damaged in any way.
Check that the information on the characteristics plate coincide with those of the ordered model.
6.3. INSULATION TESTS
•
Progressively apply 2000 RMS volts between each group of terminals indicated below and the case during one
second.
DURING ALL TESTS, TERMINALS A9 AND B9 SHALL BE
DISCONNECTED
•
The independent relay groups are as follows:
Group 1:
A10, B10
Power supply
Group 2:
A1 to A6, B1 to B4
Voltage transformers
Group 3:
C9 to C12, D9 to D12
Digital inputs
Group 4:
C9, C10, D9, D10
Inputs group 1
Group 5:
A11, B11
Trip 1
Group 6:
A12, B12
Trip 2
Group 7:
C1, D1
Trip 3
Group 8:
C2, D2
Trip 4
Group 9:
C4, D4
Trip 5
Содержание MOV 2000
Страница 3: ......
Страница 7: ...TABLE OF CONTENTS 4 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 9: ...1 GENERAL DESCRIPTION AND APPLICATION 6 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 33: ...3 SETTINGS 30 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 37: ...4 TECHNICAL CHARACTERISTICS 34 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 41: ...5 HARDWARE DESCRIPTION 38 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 57: ...6 ACCEPTANCE TESTS 54 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 59: ...7 INSTALLATION AND MAINTENANCE 56 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 71: ...8 KEYPAD AND DISPLAY 68 MIV Digital Multifunctional Protective Relay GEK 106271 ...
Страница 72: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 69 FIGURES FIGURES FIGURES FIGURES ...
Страница 73: ...FIGURES 70 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 1 PANEL MOUNTING DIAGRAM 226B6086H10 ...
Страница 74: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 71 FIGURE 2 FRONT VIEW 226B7412H9 ...
Страница 75: ...FIGURES 72 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 3 EXTERNAL CONNECTIONS 189C4129 H1 ...
Страница 77: ...FIGURES 74 MIV Digital Multifunctional Protective Relay GEK 106271 FIGURE 6 REAR VIEW 226B7412H10 ...
Страница 78: ...FIGURES GEK 106271 MIV Digital Multifunctional Protective Relay 75 FIGURE 7 DIMENSIONS DIAGRAM 226B6086H10 ...