469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
COMMUNICATIONS GUIDE
1952
RTD #9 high alarm level
1
250
1
°C
F1
80
1953
Reserved
1954
RTD #10 high Alarm
0
2
1
--
F115
0
1955
RTD #10 high alarm relays
0
6
1
--
F113
0
1956
RTD #10 high alarm level
1
250
1
°C
F1
80
1957
Reserved
1958
RTD #11 high alarm
0
2
1
--
F115
0
1959
RTD #11 high alarm relays
0
6
1
--
F113
0
195A
RTD #11 high alarm level
1
250
1
°C
F1
80
195B
Reserved
195C
RTD #12 high alarm
0
2
1
--
F115
0
195D
RTD #12 high alarm relays
0
6
1
--
F113
0
195E
RTD #12 high alarm level
1
250
1
°C
F1
60
195F
Reserved
UNDER
VOLTAGE
1960
Undervoltage active only if bus energized
0
1
1
--
F103
0
1961
Undervoltage alarm
0
2
1
--
F115
0
1962
Undervoltage alarm relays
0
6
1
--
F113
0
1963
Undervoltage alarm pickup
60
99
1
×
Rated
F3
85
1964
Starting undervoltage alarm pickup
60
100
1
1
×
Rated
F3
85
1965
Undervoltage alarm delay
0
600
1
s
F2
30
1966
Undervoltage alarm events
0
1
1
--
F103
0
1967
Undervoltage trip
0
2
1
--
F115
0
1968
Undervoltage trip relays
0
3
1
--
F111
0
1969
Undervoltage trip pickup
60
99
1
×
Rated
F3
80
196A
Starting undervoltage trip pickup
60
100
1
1
×
Rated
F3
80
196B
Undervoltage trip delay
0
600
1
s
F2
30
196C
Undervoltage trip mode
0
1
1
--
F149
0
196D
Reserved
196E
Reserved
...
...
197F
Reserved
OVER
VOLTAGE
1980
Overvoltage alarm
0
2
1
--
F115
0
1981
Overvoltage relays
0
6
1
--
F113
0
1982
Overvoltage alarm pickup
101
120
1
×
Rated
F3
105
1983
Overvoltage alarm delay
5
600
1
s
F2
30
1984
Overvoltage alarm events
0
1
1
--
F103
0
1985
Overvoltage trip
0
2
1
--
F115
0
1986
Overvoltage trip relays
0
3
1
--
F111
0
1987
Overvoltage trip pickup
101
120
1
×
Rated
F3
110
1988
Overvoltage trip delay
5
600
1
s
F2
30
1989
Reserved
Table 7: 469 MEMORY MAP (Sheet 40 of 90)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT