48
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
COMMUNICATIONS GUIDE
15E4
Time to trip at 8.00 x FLA
5
999999
1
s
F10
56
15E6
Time to trip at 10.0 x FLA
5
999999
1
s
F10
56
15E8
Time to trip at 15.0 x FLA
5
999999
1
s
F10
56
15EA
Time to trip at 20.0 x FLA
5
999999
1
s
F10
56
15EC
Reserved
15ED
Reserved
...
...
15FF
Reserved
1600
Minimum allowable line voltage
70
95
1
%Rated
F1
80
1601
Stall current at minimum Vline
200
1500
1
×
FLA
F3
480
1602
Safe stall time at minimum Vline
5
9999
1
s
F2
200
1603
Acceleration intersect at minimum Vline
200
1500
1
×
FLA
F3
380
1604
Stall current at 100% Vline
200
1500
1
×
FLA
F3
600
1605
Safe stall time at 100% Vline
5
9999
1
s
F2
100
1606
Acceleration intersect at 100% Vline
200
1500
1
×
FLA
F3
500
1607
Reserved
1608
Reserved
…
…
163F
Reserved
SHORT
CIRCUIT TRIP
1640
Short circuit trip
0
2
1
--
F115
0
1641
Overreach filter
0
1
1
--
F103
0
1642
Short circuit trip relays
0
6
1
--
F118
0
1643
Short circuit trip pickup
20
200
1
×
CT
F2
100
1644
Intentional short circuit trip delay
0
1000
10
ms
F1
0
1645
Short circuit trip backup
0
1
1
--
F103
0
1646
Short circuit backup relays
0
2
1
--
F119
0
1647
Short circuit trip backup delay
10
2000
10
ms
F1
200
1648
Reserved
1649
Reserved
---
---
164F
Reserved
OVERLOAD
ALARM
1650
Overload alarm
0
2
1
--
F115
0
1651
Overload alarm relays
0
6
1
--
F113
0
1652
Overload alarm events
0
1
1
--
F103
0
1653
Overload alarm delay
1
600
1
s
F2
0
1654
Reserved
1655
Reserved
...
...
165F
Reserved
MECHANICAL
JAM
1660
Mechanical jam trip
0
2
1
--
F115
0
1661
Mechanical jam trip relays
0
3
1
--
F111
0
Table 7: 469 MEMORY MAP (Sheet 30 of 90)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT