COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
51
16F4
Reserved
...
...
16FF
Reserved
RESTART
BLOCK
1700
Restart block
0
1
1
--
F103
0
1701
Restart block time
1
50000
1
s
F1
1
1702
Reserved
1703
Reserved
...
...
177F
Reserved
RTD TYPES
1780
Stator RTD type
0
3
1
--
F120
0
1781
Bearing RTD type
0
3
1
--
F120
0
1782
Ambient RTD type
0
3
1
--
F120
0
1783
Other RTD type
0
3
1
--
F120
0
1784
Reserved
1785
Reserved
...
...
178F
Reserved
RTD #1
1790
RTD #1 application
0
4
1
--
F121
1
1791
RTD #1 alarm
0
2
1
--
F115
0
1792
RTD #1 alarm relays
0
6
1
--
F113
0
1793
RTD #1 alarm temperature
1
250
1
°C
F1
130
1794
RTD #1 alarm events
0
1
1
--
F103
0
1795
RTD #1 trip
0
2
1
--
F115
0
1796
RTD #1 trip voting
1
12
1
--
F122
1
1797
RTD #1 trip relays
0
3
1
--
F111
0
1798
RTD #1 trip temperature
1
250
1
°C
F1
155
1799
1st and 2nd characters of RTD #1 name
0
65535
1
--
F22
‘ ’
1799
3rd and 4th characters of RTD #1 name
0
65535
1
--
F22
‘ ’
1799
5th and 6th characters of RTD #1 name
0
65535
1
--
F22
‘ ’
179C
7th and 8th characters of RTD #1 name
0
65535
1
--
F22
‘ ’
179D
Reserved
179E
Reserved
...
...
17AD
Reserved
17AE
RTD #1 alarm temperature (in Fahrenheit)
34
482
1
°F
F1
266
17AF
RTD #1 trip temperature (in Fahrenheit)
34
482
1
°F
F1
311
RTD #2
17B0
RTD #2 application
0
4
1
--
F121
1
17B1
RTD #2 alarm
0
2
1
--
F115
0
17B2
RTD #2 alarm relays
0
6
1
--
F113
0
17B3
RTD #2 alarm temperature
1
250
1
°C
F1
130
17B4
RTD #2 alarm events
0
1
1
--
F103
0
17B5
RTD #2 trip
0
2
1
--
F115
0
Table 7: 469 MEMORY MAP (Sheet 33 of 90)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT