COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
15
Event Recorder
The 469 event recorder data starts at address 3000h. Address 3003h is a pointer to the
event of interest (1 representing the latest event and 256 representing the oldest event). To
retrieve Event 1, write ‘1’ to the Event Record Selector (3003h) and read the data from
3004h to 3035h. To retrieve Event 2, write ‘2’ to the Event Record Selector (3003h) and read
the data from 3004h to 3035h. All 256 events may be retrieved in this manner. The time
and date stamp of each event may be used to ensure that all events have been retrieved in
order without new events corrupting the sequence of events (Event 1 should be more
recent than Event 2, Event 2 should be more recent than Event 3, etc.).
Each communications port can individually select an Event ID number by writing address
to 3003h. This allows the front port, rear port, and auxiliary port to read different events
from the event recorder simultaneously.
Waveform Capture
The 469 stores a number of cycles of A/D samples each time a trip occurs in a trace buffer.
The trace buffer is partitioned according to the
S1 PREFERENCES
TRACE MEMORY BUFFERS
setpoint. The Trace Memory Trigger is set up with the
S1 PREFERENCES
TRACE MEMORY
TRIGGER
setpoint and this determines how many pre-trip and post-trip cycles are stored.
The trace buffer is time and date stamped and may be correlated to a trip in the event
record. 10 waveforms are captured this way when a trip occurs. These are the 3 phase
currents, 3 differential currents, ground current and 3 voltage waveforms. This information
is stored in volatile memory and will be lost if power is cycled to the relay.
User Map Address #36
0123
032B
RTD #11 temperature
User Map Address #37
0124
032C
RTD #12 temperature
User Map Address #38
0125
0340
Vab
User Map Address #39
0126
0341
Vbc
User Map Address #40
0127
0342
Vca
User Map Address #41
0128
0343
Average line voltage
User Map Address #42
0129
0348
System frequency
User Map Address #43
012A
0370
Power factor
User Map Address #44
012B
0371
Real power (1st word)
User Map Address #45
012C
0372
Real power (2nd word)
User Map Address #46
012D
0374
Reactive power (1st word)
User Map Address #47
012E
0375
Reactive power (2nd word)
User Map Address #48
012F
0376
Apparent power
User Map Address #49
0130
030D
Phase A differential current
User Map Address #50
0131
030E
Phase B differential current
User Map Address #51
0132
030F
Phase C differential current
User Map Address #52
0133
02D5
Assignable switch #1 status
User Map Address #53
0134
02D6
Assignable switch #2 status
User Map Address #54
0135
02D7
Assignable switch #3 status
User Map Address #55
0136
02D8
Assignable switch #4 status
Table 1: Default assignments for User-Definable Memory Map Area