A–6
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
LM10 AND GE FANUC 90-30 WITH DEVICENET™
CHAPTER A:
A.2 LM10 and GE Fanuc 90-30 with DeviceNet™
A.2.1 Overview
This section describes an example communications setup between the LM10 Motor
Protection System and the GE Fanuc 90-30 PLC via the DeviceNet protocol.
• Explicit Messaging: for configuration and monitoring.
• All the values mentioned in DeviceNet™ object model (voltage, current, power
factor, trip class, FLA settings, etc.) can be monitored.
• Polling Input/Output Connection: commands to the slave device and status from
the slave device.
• Data for assemblies #5 and #54. With polling, the Run1 and Run 2 contactors can
be controlled. Note that only one relay output can be energized a time.
• COS (Change of State) and Cyclic Input/Output Connection: for alarm/event
notifications
Essentially, the COS/Cyclic connection is intended for monitoring the status of the Run1
and Run2 contactors.
A.2.2 GE Fanuc 90-30 PLC Hardware
The hardware for the setup example is indicated below:
• Main Rack (Base 10 Slot or Base 5 Slot IC693CHS391/7)
• Power Supply (IC693PWR XXX)
• CPU (IC693CPU XXX) except CPU321 & CPU340
• DeviceNet Master Module (IC693DNM200)
• GE Fanuc Software: Cimpilcity ME version 4.00
• DeviceNet Slave Module: GE Multilin LM10 Motor Protection System
A.2.3 Network Configuration
To connect the LM10 Motor Protection System to the DeviceNet™ master card
(IC693DNM200), refer to chapter 2 of the Series 90-30 Programmable Controller manual
(publication number GFK-2196).
A.2.4 Configuration Procedure
Z
Complete the basic setup of the rack, power supply, and CPU.
Z
Add the DeviceNet™ master card (IC693DNM200) to any non-CPU
slots 2 to 10.
Z
Start the GE Fanuc Cimpilcity ME software.
Z
Add the slave device by right-clicking on the slot containing the
DeviceNet™ master card, then click
Add Slave
.
A slave catalog will be displayed.
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...
Страница 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...