CHAPTER 4: FUNCTIONALITY
STATUS VALUES
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–39
4.3
Status Values
4.3.1
Main Menu
The main menu for the status values is shown below. Press the STATUS key to access these
values.
GE LM10 1.70
Class: 10
MAC ID: 1
Baud: 500
Status Active
Ready to Run
Range: Running 1, Running 2, Ready to
Run, Fault
Status Active
Phase A: 0.0
Range: 0.0 to 3200.0 A
Status Active
Phase B: 0.0
Range: 0.0 to 3200.0 A
Status Active
Phase C: 0.0
Range: 0.0 to 3200.0 A
Status Active
GndAmps: 0.0
Range: 0.0 to 25.0 A
Status Active
VOLTs:
220
Range: 0 to 9000 V
Status Active
PowFact: 0.00
Range: 0.00 to 1.00
Status Active
KW:
0.0
Range: 0.0 to 6553.5 kW
Status Active
Avg Cur: 0.0
Range: 0.0 to 3200.0 A
Status Active
%CurUnBl:
0
Range: 0 to 250%
Status Active
Motor Hrs: 0
Range: 0 to 65535 hours in steps of 1
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...
Страница 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...