CHAPTER A:
LM10 AND GE FANUC 90-30 WITH DEVICENET™
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
A–7
Z
Select
GE LM10
under
GE Multilin
.
If the slave is not displayed in the slave catalog, it can be added using the EDS file:
Z
Click the
Have Disk
tab in the slave catalog, then open the EDS file
for the LM10.
We can also add the slave device to the master card from Tool Chest:
Z
Click the
Tool Chest
icon in the tool bar.
Z
Open the drawer of DeviceNet™ devices, select the LM10 slave
device under the GE Multilin folder, and drag it onto the
DeviceNet™ master card.
Z
Set the
MAC ID
on LM10 module equal to the one displayed under
the
General
tab of the
Slave Properties
window.
Z
To see the slave properties window, right click on the
Slave Device
,
add it to the Master, and select
Network Setting
.
Z
Right-click on
Slot 2
where the master card is added.
Z
Select
Network Setting
to view the DN9030 master properties.
Z
Right-click on the LM10 slave device added under the master card
for
Setting Slave Properties
.
Z
Set the baud rate in DN9030 master properties window equal to
baud rate of the LM10 slave device.
The LM10 has three (3) baud rate settings: 125, 250, and 500 kbps
(125 kbps is the default value).
Z
Connect the LM10 as per
As well, energize terminal pin 21 with 120 V to enable network
control.
To determine the correct slave input register (%I00xx) and slave output register (%Q00xx),
double-click the added slaves under the master and note register 3 for connections 1 and
2.
A.2.5 Polling Input/Output Connection
Input/output messaging is for time-critical, control-oriented data. It provides a dedicated,
special purpose communication path between a producing application and consuming
application.
The Polling Input/Output Connection will accept 1 byte of command data and returns
1 byte of device status data and 6 bytes of current metering data for poll data group 1
(2 bytes each for phase A, B, and C currents).
Z
Set the network to
polling mode
on the master side.
Z
Under the
General
tab, set the baud rate equal to the baud rate of
the slave device.
Z
Also, set the
Scan Interval
and
Reconnect Time
.
Z
Select the
Polled
option under the
Connection 1
tab.
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...