CHAPTER 5: COMMUNICATIONS
DEVICENET OPERATIONS
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5–53
Connection Object, Class Code 5, Instance 2 (polled input/output connection):
Connection Object, Class Code 5, Instance 4 (COS/Cyc input/output connection):
4
Get
Produced connection ID
UINT
MAC ID
5
Get
Consumed connection ID
UINT
MAC ID
6
Get
Initial comm. characteristics
UINT
0x21
7
Get
Produced connection size
UINT
0x12
8
Get
Consumed connection size
UINT
0x12
9
Get/Set
Expected package rate
UINT
0x00
12
Get/Set
Watchdog timeout action
UINT
0x00
13
Get
Produced path length
UINT
0x0000
14
Get
Produced path
BYTE [6]
<null>
15
Get
Consumed path length
UINT
0x0000
16
Get
Consumed path
BYTE [6]
<null>
17
Get
Production inhibit timer
UINT
0x0000
Attribute
Access
Name/Description
Data type
Value
1
Get
State
BYTE
0x03
2
Get
Instance_type
BYTE
0x01
3
Get
Export class trigger
BYTE
0x80, 0x82
4
Get
Produced connection ID
UINT
MAC ID
5
Get
Consumed connection ID
UINT
MAC ID
6
Get
Initial comm. characteristics
UINT
0x01, 0xF1
7
Get
Produced connection size
UINT
0x01
8
Get
Consumed connection size
UINT
0x01
9
Get/Set
Expected package rate
UINT
0x00
12
Get/Set
Watchdog timeout action
UINT
0x00
13
Get
Produced path length
UINT
0x0006
14
Get
Produced path
BYTE [6]
*
*The Produced path will vary depending on the setting for Poll Data Group:
Poll Group 1: 0x20, 0x04, 0x24, 0x66, 0x30, 0x03 (Class 4, Inst. 102, Attr. 3)
Poll Group 2: 0x20, 0x04, 0x24, 0x67, 0x30, 0x03 (Class 4, Inst. 103, Attr. 3)
Poll Group 3: 0x20, 0x04, 0x24, 0x68, 0x30, 0x03 (Class 4, Inst. 104, Attr. 3)
Poll Group 4: 0x20, 0x04, 0x24, 0x69, 0x30, 0x03 (Class 4, Inst. 105, Attr. 3)
15
Get
Consumed path length
UINT
0x0006
16
Get
Consumed path
BYTE [6]
0x20, 0x04,
0x24, 0x64,
0x30, 0x03
17
Get
Production inhibit timer
UINT
0x0000
Attribute
Access
Name/Description
Data Type
Value
1
Get
State
BYTE
0x03
2
Get
Instance_type
BYTE
0x01
3
Get
Export class trigger
BYTE
0x00, 0x02,
0x10, 0x12
4
Get
Produced connection ID
UINT
MAC ID
5
Get
Consumed connection ID
UINT
MAC ID
6
Get
Initial comm. characteristics
UINT
0x01
Attribute
Access
Name/Description
Data Type
Value
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...
Страница 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...