5–56
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICENET OPERATIONS
CHAPTER 5: COMMUNICATIONS
The data type format codes for class code 0x64, instance 1 are shown below.
0x09
Get/set
User setting, Run 2, stall
F4
Trip, Time
0x0A
Get/set
User setting, Run 1, unbalance
F5
Trip, Time
0x0B
Get/set
User setting, Run 2, unbalance
F5
Trip, Time
0x0C
Get/set
User setting, Run 1, load loss
F6
Trip, Time
0x0D
Get/set
User setting, Run 2, load loss
F6
Trip, Time
0x0E
Get/set
User setting, power transformers
F7
0 to 11
0x0F
Get/set
User setting, current transformers
F8
1 to 15
0x10
Get/set
User setting, auxiliary sense 1 timer
F9
0.1
×
(0 to 250)
0x11
Get/set
User setting, auxiliary sense 2 timer
F10
0.1
×
(0 to 250)
0x12
Get/set
User setting, auxiliary relay flags
F11
16 bits
0x15
Get
Motor run time hours
UINT
Hours
0x1A
Get/set
Configure passcode
UINT
Code (0)
0x24
Get/set
User setting, motor type
F12
Type 0 to 5
0x25
Get/set
User setting, loops through CT
F13
1 to 4
0x26
Get/set
Flags (Mrun, AutoRestart, O/V Volt
Enable, DNFault, 50 Hz)
F14
16 bits
0x2E
Call
Reset LM10
*
N/A
---
0x1C
Call
Reset factory default user settings
N/A
---
0x2F
Get
Trip class
F17
---
0x30
Get
MAC ID
F18
---
0x31
Get
DeviceNet baud rate
F19
---
0x34
Get
Input switch status
F25
16 bits
0x38
Get
Remaining cool-down period
F26
16 bits
0x39
Get/set
Poll data group
F15
1 to 4
0x3A
Get/set
Run1-Run2 time delay
F16
0 to 600 sec.
0x3B
Get/set
Run2-Run1 time delay
2
F16
0 to 600 sec.
0x40
History
Status (send data byte 0 for current, 1
to 10 for history)
F24
---
0x41
History
Phase A current
F23
×
0.1 A
0x42
History
Phase B current
F23
×
0.1 A
0x43
History
Phase C current
F23
×
0.1 A
0x44
History
Ground current
F23
×
0.1 A
0x45
History
Voltage
UINT
volts
0x46
History
Power factor
UINT
percent
0x47
History
Watts
F23
0.1 kW
0x48
History
Operating current
F23
×
0.1 A
0x49
History
Current unbalance
UINT
percent
0x50
Login
User
---
---
0x51
Login
Configuration
UINT
Passcode
0x52
Login
Calibration
UINT
Passcode
*This call function has the same result as pressing the Reset key on the PDU display
Applies to revisions 1.50 and higher
Attribute
Access
Name/Description
Data Type
Value
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...