CHAPTER 5: CONFIGURING THE SOFTWARE
5.
Click the
Retrieve from archive
button.
Result: The Choose file dialog appears.
6.
Navigate to the folder
Configuration Files
\
ApplicationDefinitions
on the D20MX
Documentation CD, and select the zip file there. Then, click
OK
.
Result: The Import application definition screen re-appears. The Available Applications
list contains many applications.
7.
Click
Select All
and then
Next
.
Result: The Importing Application Definitions progress dialog appears momentarily.
The migration may take a few minutes.
Result: The Task completed dialog appears.
8.
Click
Next
and
Finish
.
Transfer D20/D200 configurations to the D20MX
Use this information to transfer existing D20 and D200 device configurations to the
D20MX.
NOTE
The word “transfer” is used within the context of this guide to mean that the device
configuration files are moved and modified, in order to work properly on a D20 with a
D20MX processor.
If you are transferring a D20 device configuration, follow the steps in section: “Transferring
a D20 configuration to the D20MX” on page 70.
If you are transferring a D200 device configuration, follow the steps in the following
sections:
•
Section: “Transferring a D200 configuration to the D20MX” on page 77
•
Section: “Transferring a D20 configuration to the D20MX” on page 70
Transferring a D20 configuration to the D20MX
Prerequisites
Before you can transfer a D20 device configuration, the following components must be
present:
•
SGConfig 7.2 or higher installed on the configuration computer.
•
The D20MX application definitions have been migrated to the configuration computer
using the instructions in Section:
Migrate D20MX application definitions to SGConfig
.
•
The D20MX Documentation CD (part number 588-0075 V120) installed in a CD/DVD
drive of the configuration computer.
•
D20 Configuration has been migrated to SGConfig with the Migration Wizard (Refer to
the Migration Wizard screencast).
•
To save time, you may upgrade the firmware definition of your D20 or D200
Configuration to SAN0001 or SAN0002 in ConfigPro
TM
. If you choose to take this
option, follow the instructions provided in Section: “Updating D20/D200 configurations
to use the D20MX firmware definition with ConfigPro” on page 78, before migrating
the D20 configuration to SGConfig.
•
A NULL modem cable (GE part number 977-0529) connecting the RS-232 connector
on the front panel of the D20MX to the serial communications port of the
configuration computer.
Содержание D20MX
Страница 6: ...6 GENERAL D20MX HARDWARE USER S MANUAL TABLE OF CONTENTS...
Страница 10: ...10 GE INFORMATION D20MX HARDWARE USER S MANUAL ABOUT THIS DOCUMENT...
Страница 30: ...30 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 1 BEFORE YOU START...
Страница 40: ...40 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 2 INSTALLING THE D20MX...
Страница 54: ...54 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 3 CONNECTING TO DEVICES AND NETWORKS...
Страница 100: ...100 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX B STANDARDS PROTECTION...
Страница 136: ...136 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX D USING CONFIGPRO WITH D20MX...
Страница 140: ...140 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX E LIST OF ACRONYMS...
Страница 144: ...144 GENERAL D20MX HARDWARE USER S MANUAL INDEX...
Страница 146: ...146 GE INFORMATION D20MX HARDWARE USER S MANUAL...