50
GE INFORMATION
D20MX HARDWARE USER’S MANUAL
CHAPTER 3: CONNECTING TO DEVICES AND NETWORKS
Figure 19: Redundant D20 system with CCU A active
If the Active CCU fails:
•
The Standby CCU detects the failure through the inter-CCU communications link.
•
The Standby CCU commands the RS-232 Switch Panel to switch over all serial
connections.
•
The RS-232 Switch Panel switches all serial field connections to the Standby CCU,
which now becomes the Active CCU.
If CCU A fails, CCU B becomes active. See Figure 20, “Redundant D20 system - If CCU A
fails”.
Figure 20: Redundant D20 system - If CCU A fails
RS-232 Switch Panel
CCU A
(Active)
CCU B
(Standby)
CCU B Serial
Communications
CCU A Serial
Communications
To Field Equipment
Inter-CCU
Communications
RS-232 Switch
Monitor and Control
RS-232 Switch Panel
CCU A
(F ailed)
CCU B
(Active)
CCU B Serial
Communications
CCU A Serial
Communications
To Field Equipment
Inter-CCU
Communications
RS-232 Switch
Monitor and Control
Содержание D20MX
Страница 6: ...6 GENERAL D20MX HARDWARE USER S MANUAL TABLE OF CONTENTS...
Страница 10: ...10 GE INFORMATION D20MX HARDWARE USER S MANUAL ABOUT THIS DOCUMENT...
Страница 30: ...30 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 1 BEFORE YOU START...
Страница 40: ...40 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 2 INSTALLING THE D20MX...
Страница 54: ...54 GE INFORMATION D20MX HARDWARE USER S MANUAL CHAPTER 3 CONNECTING TO DEVICES AND NETWORKS...
Страница 100: ...100 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX B STANDARDS PROTECTION...
Страница 136: ...136 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX D USING CONFIGPRO WITH D20MX...
Страница 140: ...140 GE INFORMATION D20MX HARDWARE USER S MANUAL APPENDIX E LIST OF ACRONYMS...
Страница 144: ...144 GENERAL D20MX HARDWARE USER S MANUAL INDEX...
Страница 146: ...146 GE INFORMATION D20MX HARDWARE USER S MANUAL...