4
–
Clearing the oscillography records
–
Changing the date and time
–
Clearing the breaker arcing current
–
Clearing the data logger
–
Clearing the user-programmable pushbutton states
To enter the initial setting or command password:
1.
Press the
MENU
key until the
SETTINGS
header flashes momentarily and the
PRODUCT SETUP
message appears on the
display.
2.
Press the
MESSAGE
right arrow until the
ACCESS LEVEL
message appears on the display.
3.
Press the
MESSAGE
down arrow until the
CHANGE LOCAL PASSWORDS
message appears on the display.
4.
Press the
MESSAGE
right arrow until the
CHANGE SETTING PASSWORD
or
CHANGE COMMAND PASSWORD
message
appears on the display.
5.
After the
CHANGE...PASSWORD
message appears on the display, press the
VALUE
up or down arrow to change the
selection to “Yes.”
6.
Press the
ENTER
key and the display prompts you to
ENTER NEW PASSWORD
.
7.
Type in a password and press the
ENTER
key.
8.
When
VERIFY NEW PASSWORD
displays, re-type the password and press
ENTER
.
9.
When the
NEW PASSWORD HAS BEEN STORED
message appears, your new Setting (or Command) password is active.
4.2.11 Invalid password entry
By default, when an incorrect Command or Setting password has been entered via the front panel three times within five
minutes, the
LOCAL ACCESS DENIED
FlexLogic operand is set to “On” and the B30 does not allow settings or command level
access via the front panel for five minutes.
By default, when an incorrect Command or Setting password has been entered via any external communications interface
three times within five minutes, the
REMOTE ACCESS DENIED
FlexLogic operand is set to
“
On
”
and the B30 does not allow
settings or command access via the any external communications interface for five minutes. The
REMOTE ACCESS DENIED
FlexLogic operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings password.
These default settings can be changed in EnerVista under
Settings > Product Setup > Security
.
4.3 Logic diagrams
Logic diagrams in this instruction manual provide an overview of function and settings. A logic diagram is based on
SECURITY
ACCESS LEVEL:
Restricted
CHANGE LOCAL
PASSWORDS
CHANGE COMMAND
PASSWORD: No
CHANGE SETTING
PASSWORD: No
CHANGE SETTING
PASSWORD: No
CHANGE SETTING
PASSWORD: Yes
ENTER NEW
PASSWORD: ##########
VERIFY NEW
PASSWORD: ##########
NEW PASSWORD
HAS BEEN STORED
Содержание b30
Страница 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 50: ...2 36 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 208: ...4 86 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 441: ...CHAPTER 5 SETTINGS CONTROL ELEMENTS B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL 5 233 5 Figure 5 123 Time out mode ...
Страница 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 514: ...6 28 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 528: ...7 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 554: ...9 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL OUTPUT LOGIC AND EXAMPLES CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 600: ...A 16 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 608: ...C 6 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...