CHAPTER 5: SETTINGS
PRODUCT SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-71
5
Navigate to
Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1
to access the settings that specify the messages to be accepted by the first RxGOOSE element. The settings
and functionality for the other RxGOOSE are similar. The following settings are available. They allow RxGOOSE1 to
recognize the GOOSE messages it is to accept. Most of these settings are automatically configured by UR Setup software
when an association to an RxGOOSE Boolean Input, RxGOOSE DPS Input, and/or RxGOOSE Analog Input is made as
described in the sections following this. Only settings
R-RxGOOSE1 RECEPTION MODE
,
R-RxGOOSE1 SECURITY
, and
R-
RxGOOSE SRC IP
need to be manually completed as the information is not contained in publisher SCL.
Figure 5-28: IEC 61850 RxGOOSE Messages panel
RxGOOSE1 MODE
Range: GOOSE, R-GOOSE
Default: GOOSE
When set to GOOSE, TxGOOSE1 messages are published in IEC 61850 8 1:2011 GOOSE format. When set to R-GOOSE,
TxGOOSE1 messages are published in Routable GOOSE format according to IEC 61850 90-5. When set to R-GOOSE, the
R-RxGOOSE DST IP
needs to be a valid multicast or unicast IP address.
RxGOOSE1 goID
Range: 0 to 129 Visible String characters
Default: empty string
If the entered value has one or more characters, the goID field of incoming GOOSE messages must exactly match this
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field.
If the publisher is a UR 7.3x series device, this setting needs match the value of the publisher's
TxGOOSE GoID
setting.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 01-0C-CD-01-00-00
When the
RxGOOSE1 MODE
setting is R-GOOSE, the value of this setting is not used, the destination Media Access
Control (MAC) address for RxGOOSE1 messages is calculated based on the
RxGOOSE DST IP
address. Otherwise, set this
setting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this value
are accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.
If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s
TxGOOSE DST MAC
setting.
Содержание b30
Страница 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 50: ...2 36 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 208: ...4 86 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 441: ...CHAPTER 5 SETTINGS CONTROL ELEMENTS B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL 5 233 5 Figure 5 123 Time out mode ...
Страница 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 514: ...6 28 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 528: ...7 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 554: ...9 14 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL OUTPUT LOGIC AND EXAMPLES CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 600: ...A 16 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 608: ...C 6 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...