Failure indication section
(Main board)Yellow indicator flashes 1 time
Compressor is running (this is normal condition
and the display of indoor unit is normal)
(Main board)Yellow indicator flashes 2 times
Defrost(normal indication of indoor unit)
(Main board)Yellow indicator flashes 3 times
Anti-freezing protection (display of indoor unit
displays is normal)
(Main board)Yellow indicator flashes 4 times
IPM module protection (corresponds to H5 of
indoor unit)
(Main board)Yellow indicator flashes 5 times
Over current protection (corresponds to E5 of
indoor unit)
(Main board)Yellow indicator flashes 5 times
Overload protection (corresponds to H4 of indoor
unit)
(Main board)Yellow indicator flashes 7 times
Discharge protection (corresponds to E4 of indoor
unit)
Indicator display at
outdoor unit
(Main board)Yellow indicator flashes 8 times
Compressor overload protection (corresponds to
H3 of indoor unit)
(Main board)red indicator flashes 1 time
Cooling (dehumidifying) current
≥
B(unit 25 B=7A,
unit 35 B=8A
)
, or heating current
≥
X(unit 25
X=8A, unit 35 X=11A
)
. Compressor is running
normally in limited frequency and display of indoor
unit is normal.
(Main board)red indicator flashes 2 times
Discharge temperature
≥
103 .
℃
Compressor is
running normally in limited frequency and display
of indoor unit is normal.
(Main board)red indicator flashes 3 times
Pipe temperature
≥
55
℃。
Compressor is running
normally in limited frequency and display of indoor
unit is normal.
(Main board)red indicator flashes 4 times
Tevap
≤
2
℃。
Compressor is running normally in
limited frequency and display of indoor unit is
normal.
(Main board)red indicator flashes 5 times
Malfunction of outdoor condenser sensor
(corresponds to F4 of indoor unit)
(Main board)red indicator flashes 6 times
Malfunction of outdoor environmental sensor
(corresponds to F3 of indoor unit)
(Main board)red indicator flashes 7 times
Malfunction of outdoor discharge sensor
(corresponds to F5 of indoor unit)
(Main board)red indicator flashes 8 times
Starting temperature is reached. This is normal
condition and display of indoor unit is normal
Indicator display
at outdoor unit
(Main board)green indicator does not flash
Communication malfunction (corresponds to E6 of
indoor unit)
Содержание AIR 326
Страница 2: ... 1 Summary and features Model Remark PRO AIR 107 IN PRO AIR 107 OUT 1Ph 230V 50Hz R410A 1 ...
Страница 4: ... 3 Model Remark PRO AIR 218 IN PRO AIR 218 OUT 1Ph 230V 50Hz R410A ...
Страница 5: ... 4 Model Remark GE AIR 326 IN1 GE AIR 326 IN2 GE AIR 326 OUT 1Ph 230V 50Hz R407C ...
Страница 6: ... 5 Model Remark GE AIR 428 IN GE AIR 428 OUT 1Ph 230V 50Hz R407C ...
Страница 20: ... 19 4 2 Outline and installation dimensions of indoor unit 20 Handle 60cm Bolt Nut Spanner ...
Страница 21: ... 20 4 3 Outline and installation dimensions of indoor units 25 32 Handle Unit mm 500 Bolt Nut Spanner ...
Страница 71: ... 70 Explosive view and parts list Explosive view of parts and components of indoor unit 9 ...
Страница 75: ... 74 Explosive view of parts and components of outdoor unit ...
Страница 77: ... 76 Explosive view of parts and components of outdoor unit frequency converter ...
Страница 79: ... 78 Explosive view of parts of outdoor unit one driving two ...
Страница 81: ... 80 Explosive view of parts of outdoor unit one driving three ...
Страница 83: ... 82 Explosive view of parts of outdoor unit one driving four ...
Страница 101: ... 100 ...