CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
Function
Setting
H-20 Motor
Feedback Loss
Function
[1] Warning
H-21 Motor
Feedback Speed
Error
100 RPM
H-22 Motor
Feedback Loss
Timeout
5 sec
LC-00 Logic
Controller Mode
[1] On
LC-01 Start Event
[19] Warning
LC-02 Stop Event
[44] Reset
key
LC-10 Comparato
r Operand
[21] Warning
no.
LC-11 Comparato
r Operator
[1] ≈*
LC-12 Comparato
r Value
90
LC-51 Logic
Controller Event
[22]
Comparator 0
LC-52 Logic
Controller Action
[32] Set
digital out A
low
E-24 Function
Relay
[80] Logic
Controller
digital output
A
* = Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 will be issued. The monitors
Warning 90 and in the case
that Warning 90 becomes TRUE,
then Relay 1 is triggered.
External equipment may then
indicate that service may be
required. If the feedback error
goes below the limit again
within 5 sec., then the drive
continues and the warning
disappears. But Relay 1 will still
be triggered until [Reset] on
the keypad.
Table 6.9 Using Logic Controller to Set a Relay
Application Set-up Examples
AF-600 FP Design and Installation Guide
6-4
DET-768A
6
6
Содержание AF-600 FP Series
Страница 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Страница 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Страница 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Страница 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Страница 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Страница 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Страница 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Страница 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Страница 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Страница 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...