12.2 General Technical Data
Line power supply (L1, L2, L3)
Supply voltage
380–480 V
±
10%
Supply voltage
525–600 V
±
10%
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at AC line voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
50/60 Hz
±
5%
Max. temporary imbalance between line phases
3.0% of rated supply voltage
True Power Factor (
λ
)
≥
0.9 nominal at rated load
Displacement Power Factor (cos
φ
) near unity
(> 0.98)
Switching on input supply L1, L2, L3 (power-ups)
maximum once/2 min.
Environment according to EN60664-1
overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100 k RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
0–100% of supply voltage
Output frequency
0–800* Hz
Switching on output
Unlimited
Accel/Decel Times
1–3,600 s
* Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
maximum 110% for 1 min.
*
Starting torque
maximum 135% up to 0.5 s
*
Overload torque (Constant torque)
maximum 110% for 1 min.
*
*Percentage relates to AF-600 FP Drive's nominal torque.
Cable lengths and cross-sections for control cables
Max. motor cable length, shielded
500 ft [150 m]
Max. motor cable length, non-shielded
1000 ft [300 m]
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
1.5mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves
1mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
0.5mm
2
/20 AWG
Minimum cross-section to control terminals
0.25mm
2
/ 24AWG
Digital inputs
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29, 32, 33,
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic'0' PNP
<
5 V DC
Voltage level, logic'1' PNP
>
10 V DC
Voltage level, logic '0' NPN
>
19 V DC
Voltage level, logic '1' NPN
<
14 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Specifications
AF-600 FP Design and Installation Guide
12-12
DET-768A
12
2
Содержание AF-600 FP Series
Страница 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Страница 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Страница 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Страница 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Страница 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Страница 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Страница 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Страница 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Страница 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Страница 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...