limit the energy into the drive to an equal or lower level
than the compliant circuit breakers.
If fuses/circuit breakers according to recommendations are
chosen, possible damage to the adjustable frequency drive
will mainly be limited to damage inside the unit.
12.3.3 CE Compliance
Fuses or circuit breakers are mandatory to comply with IEC
60364. GE recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of
delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or
500 V, or 600 V depending on the adjustable frequency
drive voltage rating. With the proper fusing the adjustable
frequency drive short circuit current rating (SCCR) is
100,000 Arms.
12.3.4 Fuse Specifications
AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1
gG-16
gG-25
1.5/2
2.2/3
3.7/5
gG-20
gG-32
5.5/7.5
gG-50
gG-63
7.5/10
11/15
15/20
gG-80
gG-125
18.5/25
22/30
gG-125
gG-150
30/40
aR-160
aR-160
37/50
aR-200
aR-200
45/60
aR-250
aR-250
Table 12.5 200–240 V, IP20/Open Chassis
AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1
gG-20
gG-32
1.5/2
2.2/3
3.7/5
5.5/7.5
gG-63
gG-80
7.5/10
11/15
15/20
gG-80
gG-100
18.5/25
gG-125
gG-160
22/30
30/40
aR-160
aR-160
37/50
aR-200
aR-200
45/60
aR-250
aR-250
Table 12.6 200–240 V, IP55/Nema 12 and IP66/Nema 4X
AF-600 3-
phase
Recommended fuse
size
Recommended max
fuse
[kW]/[HP]
0.75/1
gG-16
gG-25
1.5/2
2.2/3
3.7/5
5.5/7.5
gG-20
gG-32
7.5/10
11/15
gG-50
gG-63
15/20
18.5/25
22/30
gG-80
gG-125
30/40
37/50
45/60
gG-125
gG-150
55/75
aR-160
aR-160
75/100
aR-250
aR-250
90/125
110/150
gG-300
gG-300
132/200
gG-350
gG-350
160/250
gG-400
gG-400
200/300
gG-500
gG-500
250/350
gG-630
gG-630
315/450
aR-700
aR-700
355/500
aR-900
aR-900
400/550
450/600
500/650
aR-1600
aR-1600
560/750
630/900
aR-2000
aR-2000
710/1000
800/1200
aR-2500
aR-2500
1000/1350
Table 12.7 380–480 V, IP20/Open Chassis
Specifications
AF-600 FP Design and Installation Guide
DET-768A
12-17
12
12
Содержание AF-600 FP Series
Страница 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Страница 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Страница 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Страница 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Страница 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Страница 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Страница 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Страница 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Страница 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Страница 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...