CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.10.3
10.2.3 Enrolling the CS320 auxiliary power module
1.
Set DIP switches 1-3 to the correct address.
2.
Select
Enrol Modules>Enrol
and press
OK
. to enrol the CS320 auxiliary power module. The enrolling
process takes about 12 seconds. User codes are not accepted during the enrolling process.
10.3 Programming the CS320 auxiliary power module
You must enroll and default the CS320 power module before you begin to program the system. For more information
on enrolling and defaulting, see
Enrolling the CS320 auxiliary power module
above
and chapter B-1
Enrolling
modules
. To program the CS320 power module, select
Installer Menu>CS320 Power Modules.
10.3.1 Configuring outputs
You can specify events and partitions that can activate a particular output. The outputs are triggered based on different
events. The events are grouped in the programming tree. A full list of all possible selectable events can be found in
Table 10-3:
CS320 power module output events
. You can also assign a defined attribute to the output. The following
example enables user code 1 to reset the timer on output 1, power module 84 when an autotest event occurs.
1.
Navigate with the
µ¶
keys to
CS320 Power Modules>Power Module 84>Outputs
and press
OK
.
2.
Scroll to
Output 1>Event>Tests>Automatic Test
and press
OK
.
3.
The keypad beeps once to accept the change and returns to
Tests
.
4.
Scroll to
Attributes>Code Stops Timer>Yes
and press
OK
.
5.
The keypad beeps once to accept the change and returns to
Code Stops Timer
.
6.
Navigate with the
µ¶
keys to
Users
>
(1) User 1>Outputs
> and press
OK
.
7.
Press the relevant keys to select output 1 only and press
OK
.
8.
The keypad beeps once to accept the change and returns to
Outputs
.
Time Unit
Time
Partitions
Outputs
Power Module 84
Feature Select
Mains Delay Time
Battery Test
Battery Test Time
Reports
1 (<Event>)
Event
Alarms
Arm/Disarm
Communications
Keypads
Sirens
Tamper/Trouble
Tests
Miscellaneous
Attributes
Latched
Code Stops Timer
Inverted
Disable on Listen-in
Report Mains Fault Always
Low Battery
Siren Tamper/Trouble
Users
(1) User 1
Outputs
10.1
10.1.1
10.1.2
10.1.3
10.1.4
10.1.5
10.1.6
10.1.1.1
10.1.2.1
10.1.3.1
10.1.3.3
10.1.3.2
10.1.3.4
10.1.1.1.1
10.1.1.1.2
10.1.1.1.3
10.1.1.1.4
10.1.1.1.5
10.1.2.1.1
10.1.3.4.1
10.1.3.4.2
10.1.3.4.3
10.1.1.1.1.1
10.1.1.1.1.8
10.1.1.1.1.7
10.1.1.1.1.6
10.1.1.1.1.5
10.1.1.1.1.4
10.1.1.1.1.3
10.1.1.1.1.2
10.1.1.1.5.1
10.1.1.1.5.4
10.1.1.1.5.3
10.1.1.1.5.2
Power Modules 85 - 91
Same as above
Outputs 2 - 3
Same as above
Users 2 - 99
Same as above
If more than 10 users,
users are first displayed in
groups of 10 and then
displayed as above.
Model
Version
Default Settings