CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.2.29
2.6.1.3.1
Internal Siren Timeout
A menu option that sets the length of time the internal siren rings before
automatically cutting out. This time can be between 0 and 255 minutes. When
set to 0, the siren is active until a valid code is entered on the keypad.
2.6.1.3.2
External Siren Timeout
A menu option that sets the length of time an external sounder/siren rings
before automatically cutting out. A new alarm trip reactivates the external
sounder for the length of time specified in this option. This time can be
between 0 and 255 minutes. When set to 0, the siren is active until a valid
code is entered on the keypad.
2.6.1.3.3
Chime Time
A menu option that sets the length of time that the chime operates. This time
can be set in 50 ms (1/20th second) increments from 0-12 seconds. 0 =
follows zone.
2.6.1.4
Communications
A menu option that groups timers for communication events.
2.6.1.4.1
Phone Line Cut Delay
A menu option that sets the length of time before a phone line cut is signalled
after a phone line cut is detected.
A phone line fault is displayed in Service Check>Reset when Phone Line Cut
Delay = 0.
2.6.2
Feature Select
A menu entry that groups all optional features relating to control panel system
settings.
2.6.2.1
Inputs
A menu entry that groups options that enable features relating to inputs.
2.6.2.1.1
On-board 8 zones
A menu option that disables the zones on the control panel. This provides a
completely wireless alarm system.
2.6.2.1.2
Box Tamper
A menu option that enables the box tamper switch on the control panel. The
CSx75 has an input for a normally closed tamper switch. When opened, a box
tamper is reported as an event.
2.6.2.1.3
2-wire Smoke Detectors
A menu option that enables the 2-wire smoke detector in the control panel. A
2-wire smoke detector is connected to the control panel with two wires instead
of four. A maximum number of three 2-wire smoke detectors can be
connected.
2.6.2.1.4
Force Default Zone Types
A menu option that uses the default zone types in the country defaults for the
selected country rather than configured zone types.
2.6.2.2
Diagnostics
A menu entry that groups test options. These options specify the tests that can
be performed on the control panel.
2.6.2.2.1
Batt Presence Test
A menu option that enables a test to determine whether the battery is
connected to the system. This test is usually performed automatically when
the system is first powered up and periodically thereafter.
2.6.2.2.2
Dynamic Batt Test at Arming
A menu option that enables a dynamic battery test at arming. This is an
automatic test carried out by the control panel at the moment of arming to
ensure the battery is working properly. The panel lowers the battery charging
voltage in order to draw current from the battery. If the system is not armed
between 00:01 and 23:59, the test is performed at 00:00.
2.6.2.2.3
Manual Siren Test
A menu option that activates the siren test when the Do Self Test command is
selected from the user menu.
2.6.2.2.4
Manual Dialler Test
A menu option that includes a dialler test in the user’s manual test. A manual
test call is made to the central station and the corresponding signal is
transmitted.
2.6.2.2.5
Walktest
A menu option that enables walktest mode. This mode allows an authorised
user to test the detection devices and to verify that all zone inputs operate
correctly.
2.6.2.3
Clock
A menu entry that groups options that configure the clock.
Location
Term