CS875-575-375-275-175 Installers Manual with CS5500 keypad
B.8.3
8.3.1 Enabling memory transfer using the CS5500 keypad
The following example uses the CS5500 keypad to copy the control panel’s programming memory to the CS586
programming memory 2. It then copies programming information from the CS586 programming memory 3 to
the control panel.
1.
Navigate with the
µ¶
keys to
CS586 Direct Connect Module>Files
and press
OK
.
2.
To write information from the control panel to the CS586, scroll to
File 2>Panel to File
and press
OK
.
3.
Select
Yes
to confirm and press
OK
.
4.
The control panel’s programming memory is copied to the CS589 direct connect module’s programming
memory 2. The Receiving Data LED on the CS586 direct connect module flashes while the data is received.
The keypad sounder chimes when the operation is successful.
5.
To read information from the CS586 to the control panel, scroll to
File 3>File to Panel
and press
OK
.
6.
Select
Yes
to confirm and press
OK
.
7.
The information in the CS586 programming memory 3 is copied to the current control panel. The Sending
Data LED on the CS586 direct connect module flashes while the data is received. The keypad sounder
chimes when the operation is successful.
8.
A triple beep sounds if any error occurs when reading or sending data.
8.3.2 Enabling memory transfer using UDx75 software
The following example uses UDx75 software to copy the control panel’s programming memory to the CS586
programming memory 2. It then copies programming information from the CS586 programming memory 3 to
the control panel.
1.
Start the UDx75 upload/download software.
2.
The
UDx75 Master access
screen opens. Enter the operator name and password and press
OK
. The default
name and password in the program when it is shipped is
Operator
Aritech and
Password
1278.
3.
The
UDx75 Operator access
screen opens. Enter the operator name and password and press
OK
. The
default name and password in the program when it is shipped is
Operator
Aritech and
Password
1278.
4.
Select
Program>Setup>Direct connect settings
and press
OK
.
5.
Select the correct port number and baud rate and press
OK
. The protocol must be binary (default). The baud
rate should match the CS586 direct connect module. The default baud rate is 9600.
6.
Select
View>Customers>List
and choose the account to use from the
Customer list
screen.
7.
Select
Download>Connect>Write panel to 586
and download as normal. You are warned that this could
overwrite user codes if the user changed them.
8.
Select where to store the data on the CS586 direct connect module. This overwrites the existing data without
further prompting.
9.
A screen opens indicating that the data is being sent. When this screen disappears, the process is complete.
10. Select
Download>Read panel from 586
.
11. Select which data should be retrieved on the CS586 direct connect module.
12. A screen opens showing that the data is being read. When this screen disappears, the process is complete.