CHAPTER 6: SETPOINTS
S3 PROTECTION
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–63
Phase instantaneous overcurrent (50P)
The 345 relay has two identical instantaneous overcurrent protections - Phase IOC1, and
Phase IOC2 per protection group. Each of them consists of three separate instantaneous
overcurrent relays; one per phase, with identical settings. .
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
SETPOINTS > S3 PROTECTION > S3 SETPOINT GROUP 1(2) > S3 PHASE IOC1(2)
PH IOC1(2) FUNCTION
Range: Disabled, Latched Alarm, Alarm, Trip
Default: Disabled
For details see
Common setpoints
.
PH CT INPUTS
Range: CT(W1), CT(W2)
Default: CT(W1)
The Phase Instantaneous Overcurrent menu provides a selection for either CT(W1) input
currents or CT(W2) currents. If CT(W1) is selected, the PH IOC element will use the ratings
of the Winding 1 CTs entered on the relay under SYSTEM SETUP/S2 CURRENT SENSING. If
the CT(W2) setting is selected, the relay will use the CT ratings associated with
transformer Winding 2.
PH IOC1(2) PKP
Range: 0.05 to 20.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
This setting sets the instantaneous overcurrent pickup level. For example, a PKP setting
of 0.9 x CT with 300:5 CT translates into 270A primary current.
PH IOC1(2) DELAY
Range: 0.00 to 300.00 sec in steps of 0.01 sec
Default: 0.00 sec
This setting provides selection for the time delay used to delay the protection operation.
RLY1 TRIP W1 BKR and RLY2 TRIP W2 BKR
Range: Do not operate, Operate
Default: Do not operate
The menu for the two trip output relays - RLY1 TRIP W1 BKR and RLY2 TRIP W2 BKR - is
available only if the
Trip
setting is selected as the function for the Phase Instantaneous
Overcurrent element. One or both trip output relays can be selected to operate upon
Phase IOC operation.
NOTE
NOTE:
The "RLY1 TRIP W1 BKR" and "RLY2 TRIP W2 BKR" setpoints will be displayed on the OC
menu regardless of the selected OC function. These output relays will not operate if either
Alarm
or
Latched Alarm
is selected as an OC function, regardless of the Operate/Do Not
Operate value selected. The output relays are operational only if the OC function is
selected as
Trip
.
OUTPUT RELAY X
For details see
Common setpoints
.
BLOCK 1/2/3
For details see
Common setpoints
.
Figure 6-27: Phase Instantaneous Overcurrent Protection logic diagram
Содержание 345
Страница 28: ...1 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INTERFACES SOFTWARE SETUP 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 3 35 ...
Страница 92: ...3 38 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE SETUP CHAPTER 3 INTERFACES ...
Страница 110: ...4 18 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL A4 TARGET MESSAGES CHAPTER 4 ACTUAL VALUES ...
Страница 116: ...5 6 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL QUICK SETUP SETTINGS CHAPTER 5 QUICK SETUP FRONT CONTROL PANEL ...
Страница 246: ...7 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL GENERAL MAINTENANCE CHAPTER 7 MAINTENANCE ...
Страница 254: ...A 8 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL CHANGE NOTES ...