CHAPTER 6: SETPOINTS
S4 CONTROLS
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–81
S4 Controls
Figure 6-34: Main controls menu
Change setpoint group
The 345 relay has two identical setpoint groups- Group 1 and Group 2 for all protection
elements. Switching between these two groups is available automatically by assigning an
input (contact, virtual, remote, logic element), or via communications.
Group 1 is the default setpoint group. The relay can automatically switch from Group 1
protections to Group 2 protections, and vice versa, by setting up the switching conditions
under “Change Setpoint Group”. Under some application conditions, such as an
overcurrent element pick up, it may not be desirable to change setpoint groups. A setpoint
change can also be prevented if the breaker is open, so that a fault detected before a
reclosure will not cause a group change while the breaker is open. In such cases, the user
can set a condition under “BLK GROUP CHANGE”, where if asserted, the active setpoint
group will stay active, even if the input configured to switch to the other setpoint group is
asserted. For example if the active group was Group 1 at the time of a trip, the breaker
opens, and the input configured under “BLK GROUP CHANGE” is asserted, the relay will
maintain Setpoint Group 1, even if the input “SET GROUP 2 ACTIVE” is asserted. Vice versa, if
the “BLK GROUP CHANGE” input is asserted; the relay will not switch from Group 2 to Group
1, even if the input under “SET GROUP 2 ACTIVE” is de-asserted.
The relay will default to Setpoint Group 1, if both the input “SET GROUP 2 ACTIVE” and the
blocking input “BLK GROUP CHANGE” are de-asserted.
PATH
:
SETPOINTS > S4 CONTROLS > CHANGE SPNT GROUP
SET GROUP 2 ACTIVE
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Elements 1 to 16
Default: Off
This setting selects an input used to change from Setpoint Group 1 to Setpoint Group 2,
when asserted. If no group change supervision is selected, Setpoint group 2 will stay
active as long as the “SET GROUP 2 ACTIVE” input is asserted, and will revert to Group 1,
when this input is de-asserted.
BLOCK GROUP CHANGE
For details see
Common setpoints
.
This setting defines an input that can be used to block changing setpoint groups. When
the assigned input is asserted, changing from one setpoint group to the other one is
blocked.
897767A2. cdr
S4 CONTROLS
CHANGE SETP GROUP
VIRTUAL INPUTS
LOGIC ELEMENTS
W1 BREAKER FAIL
W2 BREAKER FAIL
RESET
LOCKOUT
ٕ
Содержание 345
Страница 28: ...1 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INTERFACES SOFTWARE SETUP 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 3 35 ...
Страница 92: ...3 38 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE SETUP CHAPTER 3 INTERFACES ...
Страница 110: ...4 18 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL A4 TARGET MESSAGES CHAPTER 4 ACTUAL VALUES ...
Страница 116: ...5 6 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL QUICK SETUP SETTINGS CHAPTER 5 QUICK SETUP FRONT CONTROL PANEL ...
Страница 246: ...7 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL GENERAL MAINTENANCE CHAPTER 7 MAINTENANCE ...
Страница 254: ...A 8 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL CHANGE NOTES ...