CHAPTER 6: SETPOINTS
S6 MONITORING
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–107
RTD #1 to 12 TRIP PKP DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 2.00 s
Sets the Trip pickup delay time.
RTD #1 to 12 TRIP DPO DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 0.00 s
Sets the Trip dropout delay time.
RTD #1 to 12 TRIP VOTING
Range: Off, RTD #1 to 12
Default: Off
Sets the redundant RTD that must also exceed this RTD’s trip temperature for a trip to
occur.
OUTPUT RELAY X
For details see
Common setpoints
.
BLOCK 1 to 3
For details see
Common setpoints
.