6–54
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION
CHAPTER 6: SETPOINTS
HEAT TIME CONSTANT (
τ
H
)
Range: 3.0 to 600.0 min in steps of 0.1 min
Default: 6.0 min
This time constant is used to compute the thermal capacity when the thermal capacity
at each time-step is greater than the one computed in the previous time-step.
COOL TIME CONSTANT (
τ
C
)
Range: 1.00 to 6.00 x
τ
H
in steps of 0.01 x
τ
H
Default: 2.00 x
τ
H
This time constant is used to compute the thermal capacity when the thermal capacity
at each time-step is less than the one computed in the previous time-step.
OUTPUT RELAY X
For details see
Common setpoints
.
BLOCK 1/2/3
For details see
Common setpoints
.
NOTE
NOTE:
The thermal capacity is displayed on the relay even if the Thermal Overload Function is
set to “Disabled”.
Содержание 345
Страница 28: ...1 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 89: ...CHAPTER 3 INTERFACES SOFTWARE SETUP 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 3 35 ...
Страница 92: ...3 38 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE SETUP CHAPTER 3 INTERFACES ...
Страница 110: ...4 18 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL A4 TARGET MESSAGES CHAPTER 4 ACTUAL VALUES ...
Страница 116: ...5 6 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL QUICK SETUP SETTINGS CHAPTER 5 QUICK SETUP FRONT CONTROL PANEL ...
Страница 246: ...7 20 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL GENERAL MAINTENANCE CHAPTER 7 MAINTENANCE ...
Страница 254: ...A 8 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL CHANGE NOTES ...