2
1
、
Product overview
Automatic SF6 density relay calibrator is an intelligent SF6 density relay
calibrator. The instrument adopts high-precision pressure sensor and
high-speed A / D converter, combined with 32-bit high-performance
microprocessor, which can verify the performance of various SF6 density
relays,accurately measure the pressure value at the current temperature when
the signal acts, automatically complete the conversion of standard pressure at
any ambient temperature to 20
℃
, and can print and store the test data in real
time for reference and automatic identification Don't test for faults in the
process. The product is easy to carry,easy to operate, high accuracy, strong
stability and good reliability, which embodies the characteristics of "intelligent"
instrument.
SF6 switch is a widely used high-voltage electrical appliance in power
system. The reliable operation of SF6 switch has become one of the most
concerned issues in power supply and consumption departments. SF6 gas
density relay is an important component used to monitor the change of SF6
gas density in the operation of SF6 switch. Its performancedirectly affects the
operation safety of SF6 switch. The SF6 gas density relay in operation on site
often has some problems such as inflexible action and poor contact after a
period of time due to its unusual action. Some of them will also have poor
temperature compensation performance of the density relay. When the
ambient temperature suddenlychanges, the SF6 density relay often
misoperates. Therefore, DL / T596-1996 "preventive test code for electric
equipment" stipulates that all SF6 switch users shall regularly verify the SF6
gas density relay. From the actual operation, it is very necessary to check the
SF6 density relay and pressure gauge regularly.