9
the equivalent pressure value at 20
℃
. The equivalent pressure value at 20
℃
is the locking recovery value of the SF6 density relay.
Verification of alarm reply value:
Continue to slowly inflate the SF6
density relay at a certain speed. When the alarm relay of the density relay acts,
record the pressure value under the current ambient temperature, and convert
it into the equivalent pressure value at 20
℃
. The equivalent pressure value at
20
℃
is the alarm reply value of the SF6 density relay.
Alarm value verification:
Under the ambient temperature, when the
pressure in SF6 density relay is greater than the alarm return value, slowly
deflate at a certain speed. When the alarm relay of SF6 density relay acts,
record the pressure value under the current ambient temperature, and convert
it into the equivalent pressure value at 20
℃
. The equivalent pressure value at
20
℃
is the alarm value of SF6 density relay.
Verification of blocking value:
Continue to slowly deflate the SF6
density relay at a certain speed. When the locking relay of the SF6 density
relay acts, record the pressure value under the current ambient temperature,
and convert it to the equivalent pressure value at 20
℃
. The equivalent
pressure value at 20
℃
is the locking value of the SF6 density relay.
In the main interface, select the "density relay verification" item with the
cursor, and click "select" to enter the density relay verification program, as
shown in Figure 4: