P.E Stops Open Cycle 

OFF -  Activating the P.E input while motors are opening is ignored by the controller. 
ON -   Activating the P.E input while motors are opening causes the motors to stop. 

 

 

P

OSITION 

P.E Triggered Auto Close 

OFF -  Not selected 
ON -   Selects the P.E triggered auto-close mode which causes the motors to auto-close if the P.E input is activated 

then released. (Auto-close delay time is 0 seconds*) 

 

 

P

OSITION 

Pedestrian Auto-Close 

OFF -  No pedestrian access auto-close 
ON -   Selects auto-close in the pedestrian access mode. (Auto-close delay time is 15 seconds*) 

 

 

P

OSITION 

10 

Standard Auto Close 

OFF -  Not selected  
ON -   Selects standard auto-close mode which will close the motors after fully opening.(Auto-close delay time is 

30 seconds*) 

 

Setting Cycle Timers & Auto Close Times 

The control board has pre-set cycle times which are used to set the maximum time the controller will drive the 
motors in the open and closed directions. The pre-programmed time for the open and close cycle timer’s is 60 
seconds. The control board also has a pre-set pedestrian access time of 5 seconds which is intended to open the motor 
connected to M1 output only part way. If these default times do not suit your needs simply use the procedure below 
to adjust them. Note the same procedure can be used to adjust the auto-close times. 

1.

 

Place the slide switch into the ‘set’ position  

2.

 

Adjust the timer’s value by pressing and holding the required push button for the desired time. 

3.

 

Repeat step 2 for the next timer (if desired). 

4.

 

Place the slide switch back into the ‘RUN’ position. 

5.

 

Test operation. 

Make sure that the slide switch is placed back into the “RUN” position before testing the new timer value.  
As you can see the procedure used to set each timer’s value is the same only the push button used changes. Each 
push button is clearly labelled underneath as to which timer’s value it sets. Note when setting the OPEN, CLOSE and 
PEDESTRIAN cycle times the controller will drive the motors as if a “real” cycle is being executed. The difference 
being that the motors will stop as soon as the button is released or the limit switches are reached. The OPN status 
LED on the control board will flash at 1 second intervals to assist setting times. Note when setting the OPEN and 
CLOSE cycle times when limit switches are used, release the push button a few seconds after the limit switch cuts 
motor power. This allows for the motors to slow down over the life of the operators without the need to adjust again. 

5.         C

OMMISSIONING

 

 

 

Position the gate half way and tighten knurled knob at back of slider by hand so gate will drive. 

 

Power up board and with gate in the half way position, press transmitter or manual control switch so operator 
drives gate. 

 

The first pulse will always open gate, green LED will flash (top right hand corner) if it does not, then reverse the 
2 motor wires. 

 

Check which limit switches stop gate in each direction, adjustment of the limit switch brackets may have to be 
made. Limit switches should not switch off the gates too soon (before reaching the stops) and conversely not too 
late, so the torque limiter is operating. 

 

Tighten torque limiter knurled knob. 

 

Set open & closed travel times. 

 

Check that all safety devices work as designed and the electromagnetic lock holds the gate firmly closed (if 
fitted). 

 

Install cover using screws provided in the front and sides to hold cover firm. 

 

Provide full details to the owner concerning the operation and relevant maintenance and disconnect details

 

 

Содержание GDS 240 PP

Страница 1: ...alia from Australian quality imported components Installation and Maintenance Manual Commercial Sliding Gate Operator Model GDS 240 PP Made in Australia from Australian quality imported components A B N July N14870 Installation and Maintenance Manual Commercial Sliding Gate Operator ...

Страница 2: ... between the rack teeth and Pinion wheel Once the rack is fixed move the gate and sight the rack moving over the pinion wheel check that most of the pinion wheel meshes with the rack Make sure rack runs freely over the pinion wheel any tights spots should be corrected by adjusting the rack height Check the operator is firmly bolted down to the concrete pad Ensure stops are installed on the gate fo...

Страница 3: ...d will turn off when the limit switch is activated if not reverse both open and closed limit switch input wires Set the run timing by switching the run set switch into set with the gate at full closed position press and hold the open button until the gate operates the open limit then keep holding the button for a further 5 seconds then release Do the same on the close cycle from the full open posi...

Страница 4: ...iew of installation Conduit entry location 3 Mechanical Installation 6 4 Installation Details 7 8 CB6 Control Board Electrical Connections 5 Commissioning 8 6 CB 6 control board layout 9 7 Schematic wiring diagram 10 8 Manual release instruction 11 9 Maintenance details 12 10 Warranty 13 ...

Страница 5: ...ould cause serious injury or death Take into consideration the general installation and Check the gateposts or mounting structure has the necessary strength and rigidity to support the operator and the closing gate motion Always incorporate the appropriate Photo Electric Cells Induction Loops and any other safety devices to protect both equipment and personnel Extra caution should be employed when...

Страница 6: ...he sliding gate operator on the concrete mounting pad and using a length of rack held onto the gate rail adjust the operator at a location where the pinion gear meshes fully onto the rack 4 Ensure the pinion wheel face is parallel with the gate rail and mark the holes through the mounting plate for fixing 5 Dynabolt mounting plate to concrete pad using 12mm x 100mm dynabolts 6 Position gate operat...

Страница 7: ...oard lock output to the normally closed output Use the light relay module if fitted to switch the applied voltage to a light The load switched by the light relay module must not exceed 240v AC 30v DC 10 Amps Mode Selection Using the mode selection dip switches select the desired operating modes Note the times associated with the parameters marked with an can be changed The auto close times can be ...

Страница 8: ...N position before testing the new timer value As you can see the procedure used to set each timer s value is the same only the push button used changes Each push button is clearly labelled underneath as to which timer s value it sets Note when setting the OPEN CLOSE and PEDESTRIAN cycle times the controller will drive the motors as if a real cycle is being executed The difference being that the mo...

Страница 9: ...puts not shown 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label 9 for Limit Switch and Control Inputs Pedestrian Access Control Input 22 Light Control Relay Interface Connector 10 Open Stop Close Control Input 23 Input Status L E Ds 11 Close Control Input 24 Stop Input Jumper 12 Stop Control Input 25 Open Input Jumper 13 Open Control Input 26 PE Beam Input Jumper 14 Photoelectric Sa...

Страница 10: ......

Страница 11: ...nt the wind catching the gate and inadvertently moving the gate which may may cause accidental damage to property or person To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and It just spins either try spinning it clockwise with more force to release it off of the he...

Страница 12: ... cover particularly near corrosive General operation i e speed auto close etc normal Comments Service performed by ETAILS Failure to maintain equipment may result in injury or death and or damage to property and Recommended maintenance to be performed on the operator and gate are as follows Operator performs over 150 cycles a day each month Operator performs between 100 150 cycles a day every 2 mo...

Страница 13: ...llowing circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personnel not authorised to do so iv In respect of loss or damage caused by rough treatment v If the product is not used and maintained in accordance with instructions or recommendations listed in this In...

Отзывы: