7
4.
I
NSTALLATION
D
ETAILS
Electrical Connections
Supply
•
Connect a 10A 240v supply to din rail terminals labelled A & N. Connect earth to din rail terminal.
Control
•
If cable runs are over 10m, connect the shielded cable to the chassis.
Control Inputs
The P.E, OPN and STP inputs require a normally closed switch contact and therefore should be shorted to the COM
terminal if not used. This is done via bridging links already on the circuit board (bottom left corner) The CLS, OSC
and PED inputs require a normally open switch contact and therefore should be left unconnected if not used. All the
switch inputs of this control board including the limit switch inputs require a switch contact only. Do not connect any
switches which provide a voltage to the control board as this will damage the control board. If the inputs are 12/24v
or has long wiring associated with it use an IM-1 module to isolate it from the control board’s input. The IM-1 is
available from the manufacturer.
Powering Accessories
Accessories, which require a 24v AC supply, can be powered from the transformer output used to power the control
board and motor. However, the transformer’s current capacity must be checked to allow for the extra power required
by the accessories.
Locks & Lights
Use the lock output terminals to switch the 12 volts to an electric lock (if fitted). The load switched by the lock
output terminals must not exceed 30v AC / DC @ 5Amps. If an electro magnetic lock is used, change one wire on
the control board lock output to the normally closed output. Use the light relay module (if fitted) to switch the
applied voltage to a light. The load switched by the light relay module must not exceed 240v AC / 30v DC @ 10
Amps.
Mode Selection
Using the mode selection dip-switches select the desired operating modes. Note the times associated with the
parameters marked with an * can be changed. The auto-close times can be changed using the procedure in the
following section. See detailed instruction manual for details how to change the other parameters.
P
OSITION
1
Synchronising Delay
OFF - No delay
ON - Motor 1 starts to open 2 seconds
*
before Motor 2 & Motor 2 starts to close 2 seconds
*
before Motor 1.
P
OSITION
2
Pulse Lock Output
OFF - Lock output is activated for the entire motor drive cycle.
ON - Lock output pulses for 0.3 seconds* at the start of each drive cycle.
P
OSITION
3
Light Outputs Warning
OFF - Optional light module controls a light with timer which turns light off after 60seconds*.
ON - Optional light module controls a warning light which activates whenever motors are on.
P
OSITION
4
Swipe Mode (OSC Input)
OFF - OSC input terminal has standard Open, Close, Stop action.
ON - OSC input terminal will only open the door/gate. The input also resets the P.E triggered auto-close
mode so that the P.E input will need to be triggered again before a P.E auto-close cycle will be initiated.
P
OSITION
5
M 2 Outputs Status
OFF - The M2 output controls second motor
ON - The M2 output controls status lights
P
OSITION
6
P.E Stops Close Cycle
OFF - Activating the P.E input while motors are closing causes the motors to reverse.
ON - Activating the P.E input while motors are closing causes the motors to stop but not reverse.