background image

                                                                                                                                                                      7 

 

 
4.

           

I

NSTALLATION 

D

ETAILS

 

Electrical Connections 

 

Supply 

 

Connect a 10A 240v supply to din rail terminals labelled A & N.  Connect earth to din rail terminal. 

Control 

 

If cable runs are over 10m, connect the shielded cable to the chassis.

 

 

Control Inputs 

The P.E, OPN and STP inputs require a normally closed switch contact and therefore should be shorted to the COM 
terminal if not used.  This is done via bridging links already on the circuit board (bottom left corner) The CLS, OSC 
and PED inputs require a normally open switch contact and therefore should be left unconnected if not used. All the 
switch inputs of this control board including the limit switch inputs require a switch contact only. Do not connect any 
switches which provide a voltage to the control board as this will damage the control board. If the inputs are 12/24v 
or has long wiring associated with it use an IM-1 module to isolate it from the control board’s input. The IM-1 is 
available from the manufacturer. 

 
Powering Accessories 

Accessories, which require a 24v AC supply, can be powered from the transformer output used to power the control 
board and motor.  However, the transformer’s current capacity must be checked to allow for the extra power required 
by the accessories. 

 
Locks & Lights 

Use the lock output terminals to switch the 12 volts to an electric lock (if fitted). The load switched by the lock 
output terminals must not exceed 30v AC / DC @ 5Amps.  If an electro magnetic lock is used, change one wire on 
the control board lock output to the normally closed output.  Use the light relay module (if fitted) to switch the 
applied voltage to a light. The load switched by the light relay module must not exceed 240v AC / 30v DC @ 10 
Amps. 

 

 
Mode Selection 

Using the mode selection dip-switches select the desired operating modes. Note the times associated with the 
parameters marked with an * can be changed. The auto-close times can be changed using the procedure in the 
following section. See detailed instruction manual for details how to change the other parameters. 

 

P

OSITION 

Synchronising Delay 

OFF -   No delay  
ON -   Motor 1 starts to open 2 seconds

*

 before Motor 2 & Motor 2 starts to close 2 seconds

*

 before Motor 1. 

 

 

P

OSITION 

Pulse Lock Output 

OFF -   Lock output is activated for the entire motor drive cycle. 
ON -   Lock output pulses for 0.3 seconds* at the start of each drive cycle. 

 

 

P

OSITION 

Light Outputs Warning 

OFF -   Optional light module controls a light with timer which turns light off after 60seconds*. 
ON -   Optional light module controls a warning light which activates whenever motors are on. 

 

 

P

OSITION 

Swipe Mode (OSC Input) 

OFF -  OSC input terminal has standard Open, Close, Stop action. 
ON -   OSC input terminal will only open the door/gate. The input also resets the P.E triggered auto-close 
 

mode so that the P.E input will need to be triggered again before a P.E auto-close cycle will be initiated. 

 

P

OSITION 

M 2 Outputs Status 

OFF -  The M2 output controls second motor 
ON -   The M2 output controls status lights 

 

 

P

OSITION 

P.E Stops Close Cycle 

OFF -  Activating the P.E input while motors are closing causes the motors to reverse. 
ON -   Activating the P.E input while motors are closing causes the motors to stop but not reverse. 

 

Содержание GDS 240 PP

Страница 1: ...alia from Australian quality imported components Installation and Maintenance Manual Commercial Sliding Gate Operator Model GDS 240 PP Made in Australia from Australian quality imported components A B N July N14870 Installation and Maintenance Manual Commercial Sliding Gate Operator ...

Страница 2: ... between the rack teeth and Pinion wheel Once the rack is fixed move the gate and sight the rack moving over the pinion wheel check that most of the pinion wheel meshes with the rack Make sure rack runs freely over the pinion wheel any tights spots should be corrected by adjusting the rack height Check the operator is firmly bolted down to the concrete pad Ensure stops are installed on the gate fo...

Страница 3: ...d will turn off when the limit switch is activated if not reverse both open and closed limit switch input wires Set the run timing by switching the run set switch into set with the gate at full closed position press and hold the open button until the gate operates the open limit then keep holding the button for a further 5 seconds then release Do the same on the close cycle from the full open posi...

Страница 4: ...iew of installation Conduit entry location 3 Mechanical Installation 6 4 Installation Details 7 8 CB6 Control Board Electrical Connections 5 Commissioning 8 6 CB 6 control board layout 9 7 Schematic wiring diagram 10 8 Manual release instruction 11 9 Maintenance details 12 10 Warranty 13 ...

Страница 5: ...ould cause serious injury or death Take into consideration the general installation and Check the gateposts or mounting structure has the necessary strength and rigidity to support the operator and the closing gate motion Always incorporate the appropriate Photo Electric Cells Induction Loops and any other safety devices to protect both equipment and personnel Extra caution should be employed when...

Страница 6: ...he sliding gate operator on the concrete mounting pad and using a length of rack held onto the gate rail adjust the operator at a location where the pinion gear meshes fully onto the rack 4 Ensure the pinion wheel face is parallel with the gate rail and mark the holes through the mounting plate for fixing 5 Dynabolt mounting plate to concrete pad using 12mm x 100mm dynabolts 6 Position gate operat...

Страница 7: ...oard lock output to the normally closed output Use the light relay module if fitted to switch the applied voltage to a light The load switched by the light relay module must not exceed 240v AC 30v DC 10 Amps Mode Selection Using the mode selection dip switches select the desired operating modes Note the times associated with the parameters marked with an can be changed The auto close times can be ...

Страница 8: ...N position before testing the new timer value As you can see the procedure used to set each timer s value is the same only the push button used changes Each push button is clearly labelled underneath as to which timer s value it sets Note when setting the OPEN CLOSE and PEDESTRIAN cycle times the controller will drive the motors as if a real cycle is being executed The difference being that the mo...

Страница 9: ...puts not shown 8 Terminals for Isolated 24vAC Supply 21 Firmware Version Label 9 for Limit Switch and Control Inputs Pedestrian Access Control Input 22 Light Control Relay Interface Connector 10 Open Stop Close Control Input 23 Input Status L E Ds 11 Close Control Input 24 Stop Input Jumper 12 Stop Control Input 25 Open Input Jumper 13 Open Control Input 26 PE Beam Input Jumper 14 Photoelectric Sa...

Страница 10: ......

Страница 11: ...nt the wind catching the gate and inadvertently moving the gate which may may cause accidental damage to property or person To re engage the clutch move the gate by hand Into approx The half way position and turn the Knurled knob clockwise until it is very tight If when turning the knurled knob clockwise and It just spins either try spinning it clockwise with more force to release it off of the he...

Страница 12: ... cover particularly near corrosive General operation i e speed auto close etc normal Comments Service performed by ETAILS Failure to maintain equipment may result in injury or death and or damage to property and Recommended maintenance to be performed on the operator and gate are as follows Operator performs over 150 cycles a day each month Operator performs between 100 150 cycles a day every 2 mo...

Страница 13: ...llowing circumstances i If no proof of date of purchase can be produced ii If the product has been used in a manner beyond its design parameters iii If the product is tampered with or repaired by personnel not authorised to do so iv In respect of loss or damage caused by rough treatment v If the product is not used and maintained in accordance with instructions or recommendations listed in this In...

Отзывы: