B-5
Appendix B, Page B-5
Ventilator Start-Up Inspection And Tests - cont.
VENTILATOR START-UP INSPECTION AND TES
Ventilator Start-Up Inspection and Test Report
For Gaylord Model ELXC and ELXC-UVi Series Ventilators
Damper Test
1.
Model of Damper.
___ No Damper. No test required, proceed to next test.
___ Model GBD manual Gaylord Balancing Damper. No test required, proceed to next damper.
___ Model GEBD Gaylord Electric Balancing Damper. Proceed to Electric Balancing Damper Test.
___ Model GFBD Gaylord Fire Balancing Damper. Proceed to Gaylord Fire Balancing Damper Test.
Gaylord Electric Balancing Damper Test (Damper Model GEBD)
1.
Ventilators with this model damper, the damper opens every time the exhaust fan is turned on and
closes every time it is shut off. To test proceed as follows:
a)
With the exhaust fan off, open the Extractor Access Door and remove the Extractor under the
exhaust duct. To test, proceed as follows:
1)
With the fan off, the damper should be closed. ………………….…….. ____ Closed ____ Open
2)
Start the fan. The damper should move to the open position …………… ____ Yes ____ No
b)
Replace Extractor and close the Extractor Access Door.
Gaylord Electric Fire Balancing Damper Test (Damper Model GFBD)
1.
Caution:
Performing this test may set off the building fire alarm system and may notify the fire
department. Notify building management/maintenance and disable the building alarm system is
necessary.
2.
Ventilators with this model damper including a thermostat, that when activated by high heat or fire,
closes the damper. This test is also called an Internal Fire Mode Test. To test proceed as follows:
a)
Push the Internal Fire Mode Test button on the Gaylord Command Center. The following
should occur:
1)
The exhaust fan should be off. ……………………………………………………………. ____ Off ____ On
2)
The make-up air should be off. …………………………………………………………… ____ Off ____ On
3)
Extractor and Plenum washes should be off. ……………………………………… ____ Off ____ On
4)
If Ventilator includes UV, it should have shut off. ………………………………. ____ Off ____ On
5)
Gaylord Command Center display should read Fire In Hood. ……………… ____ Yes ____ No
b)
With the exhaust fan off, open the Extractor Access Door and remove the Extractor under the
exhaust duct. Fire Damper should have closed. .…………………………………………… ____ Yes ____ No
c)
Replace Extractor, close Extractor Access Door and start fan.
Installation Includes the Following Equipment
____ Gaylord Autostart Control.
____ Gaylord Clearair Pollution Control Unit. (RSPC)
____ Gaylord Distributor. (UDS)
____ Fire Extinguishing System. Manufacturer _____________________________________________
Содержание ELXC Series
Страница 40: ...4 6 INTENTIONALLY LEFT BLANK ...
Страница 74: ...7 1 Chapter 7 Wiring Diagrams ELXC GBD with AUTOSTART ...
Страница 75: ...7 2 Chapter 7 Wiring Diagrams ELXC GFBD with AUTOSTART ...
Страница 76: ...7 3 Chapter 7 Wiring Diagrams ELXC GBD UVi with AUTOSTART ...
Страница 77: ...7 4 Chapter 7 Wiring Diagrams ELXC GFBD UVi with AUTOSTART ...
Страница 82: ...A 5 Appendix A Page A 5 Installation Requirements cont Figure A 5 1 Typical Installation MAIN FEED PIPE ...
Страница 83: ...A 6 INTENTIONALLY LEFT BLANK ...