Operating instructions

6.7 - WARNINGS

HOW TO AVOID CORROSION IN THE FIRE WOOD BOX

The use of wood with a high moisture content (higher than
about 25%) and/or loadings not proportioned to the sy-
stem’s heat request (long OFF periods with the wood sto-
rage full) can cause considerable condensate formation
in the fire box’s internal wall.

Check, once a week, the internal steel walls of the fire box.
They must be covered by a slight layer of opaque coloured,
dry tar, with bubbles inclined to break and fall off.
On the contrary, if the tar is bright, runny and, if removed with
the fire stoke, some liquid appears, it is necessary to use wood
with a lower moisture content and/or reduce the quantity of the
wood when loading the boiler.
If, in despite of these interventions the tar does not dry, you
must inform the local After Sales Service of this.
The condensate inside the fire box causes the corrosion of the
steel plates.
Corrosion is not covered by the guarantee, because it is cau-
sed by a bad use of the boiler (wet wood, excessive loadings,
etc.).

CORROSION IN THE FLUE CIRCUIT

The flue is rich in water steam, due to combustion and the use
of wood which always retains water.
If the flue comes into contact with relatively cold surfaces (with
a minimum temperature of about 60 - 70 °C), the steam water
condensates and, in combination with other combustion pro-
ducts, originates corrosion phenomena of the metallic parts.
Every day check if there are signs of smoke condensation (black
liquid on the floor, behind the boiler). In this case you must use
a wood with a lower moisture content; check that the recircula-
tion pump is working correctly, the flue temperature at part
load, and increase the working temperature. To control the room
temperature it is therefore necessary to install a mixing valve.

The corrosion caused by flue condensation is not cove-
red by the guarantee, because it is caused by the wood’s
moisture content and the way the boiler is used.

PRECAUTIONS TO TAKE DURING BOILER OPERA-
TION

After every air adjustment , wait 5 to 10 minutes before making
a new adjustment. Once the best adjustment has been esta-
blished, at the end of the day check that the surfaces of the
combustion chamber and the door insulation are of a white
colour.
In the ash deposited in the cradle there must be only a few
unburnt embers. If the primary air is in excess, in the ash there
will be embers and small pieces of coal, the flame will burn
fast, be dry, have a cold colour and be noisier, and the output
will be excessive (paragraph 6.5).
If the primary air is insufficient the flame burn slowly, be small,
it will not touch the lower cradle and it will drag little ash; the
output will be insufficient.
If the flame is a dark orange colour, the secondary air is insuf-
ficient and the surfaces of the combustion chamber will not be
a white colour; if it is small and blue there is too much secon-
dary air.

Always open the upper loading door and the internal antismo-
ke flap slowly.
If, in despite of these precautions, some blow back will occur,
it will be necessary to use bigger pieces of wood, with a higher
moisture content, and to check that the boiler does not remain
unused for a long time (reduce the primary air - paragraph 6.5)
and make sure that the possible distortion of the cast iron fire
bars or the modification of the stainless steel grates or that the
presence of extraneous bodies (nails, metallic pieces) has not
obstructed the refractory burner’s slot.

6.8 - SUMMER OPERATION

Use of the boiler in summer for the production of only dome-
stic hot water is not advised, unless you follow these rules
meticulously:
1) Use very dry wood
2) Do not load the boiler with too much wood, load the boiler
partially, 2 or 3 times per day ,according to need.

Important.

It is absolutely wrong to load the boiler completely so as to
gain very long working periods (for
example 24 hours). Doing so the boiler (when the fan is OFF)
will produce a lot of acid condensate
and corrode the fire box.

Содержание G3 50 2S

Страница 1: ...Wood Fired Boiler Gasogen 29 93kW User Operating Instructions...

Страница 2: ...e according to the foreseen scopes it is necessary to carefully follow the instructions indicated in this manual 3 WATER TREATMENT The hardness of the mains water supply conditions the frequency with...

Страница 3: ...ustment and servicing of this appliance must be carried out by a competent quali fied person and installed in accordance with the current standards and regulations Failure to correctly install this ap...

Страница 4: ...the switch in the I position the boiler is connected to the mains electricity supply green led light illuminated and is ready to operate The recycle pump functions Mode selection keys With the switch...

Страница 5: ...about 65 C within the foreseen time control timer the fan and re cycling pump will be turned off Panel connected to the mains electricity supply but the boiler is not running Therefore repeat the lig...

Страница 6: ...sure If it is an open circuit system the pressure does not have to be restored as this occurs automatically via the water level regu lator inside the water tank If it is a sealed circuit system refer...

Страница 7: ...g this switch you can connect or disconnect the boiler from the mains electricity supply With the switch in the 0 position the boiler is not switched on green led light off With the switch in the I po...

Страница 8: ...he upper loading door has been closed With the switch 22 it is possible to select the operation mode wood or the back up gas or oil fired boiler Place the switch into the 0 position wood firing mode N...

Страница 9: ...or disconnect the sy stem pump boiler load from the mains electrical system With the switch in the 0 position the system pump is not switched on With the switch in the II position the system pump is...

Страница 10: ...u can connect or disconnect the fan from the mains electrical system Set the switch in the I position the fan is powered electrically but it will not run It will start running only after the upper loa...

Страница 11: ...ce the plastic cap The safety thermostat can intervene in case of boiler tempera ture overheating You can avoid this happening by lowering the working thermostat see above If the boiler s safety therm...

Страница 12: ...st be placed as previously described 6 3 CHECKSTO CARRY OUT BEFORE FIRING THE BOILER Before firing the boiler carry out the following checks Check that the On Off gas valve positioned upstream of the...

Страница 13: ...ore the quantity of wood burnt whilst the secondary air completes the combustion P Primary air box S Secondary air box 1 Metal ring air adjuster P S 1 S1 P1 S S P P1 C USEFUL SUGGESTIONS and LOADING E...

Страница 14: ...noisy excess of primary air P The flame must not be too small lack of primary air P If the ash does not falls down properly increase the pri mary air P If too much ash falls down reduce the primary ai...

Страница 15: ...aused by the wood s moisture content and the way the boiler is used PRECAUTIONS TO TAKE DURING BOILER OPERA TION After every air adjustment wait 5 to 10 minutes before making a new adjustment Once the...

Страница 16: ...loading Every week Remove carefully all the residues of combustion accumula ted in the fire box Clean with the brush supplied the triangular passes of the combustion chamber Remove the ashes from the...

Страница 17: ...ushing rod when the loading door is opened In this way the smoke accumulated in the firebox is aspirated and sent to the chimney directly The bypass in conclusion allows the smoke to be discharged at...

Страница 18: ...sed for long periods see paragraph 6 7 Use thicker wood logs Use up all the wood before loading a new batch Problem The boiler does not reach the requested temperature The flame is small and there is...

Страница 19: ...er does not remain unused for long periods see paragraph 6 7 Use bigger logs Use up all the wood before loading a new batch Problem The boiler does not reach the requested temperature The flame is sma...

Страница 20: ...9 5 6 8 7 8 7 1 2 4 3 10 2 1 2 4 3 9 10 2 6 5 8 7 Spare parts GASOGEN G3 25 2S GASOGEN G3 40 2S GASOGEN G3 50 2S GASOGEN G3 65 2S GASOGEN G3 80 2S Gasogen 20...

Страница 21: ...Spare parts GASOGEN G3 25 2S GASOGEN G3 40 2S GASOGEN G3 50 2S GASOGEN G3 65 2S GASOGEN G3 80 2S 14 11 13 12 15 16 17 21...

Страница 22: ...12 26955 Stone cast iron bars insulation kit 13 26956 Stone cast iron bars insulation kit X X 13 12350 Cast iron bars insulation kit 14 12352 Cast iron bars insulation kit X X X X PUC0420 Triangular...

Страница 23: ...ing Pty Ltd ABN 90 446 545 923 51 Assembly Tullamarine Vic 3043 Australia PO Box 356 Tullamarine Vic 3043 Australia 61 3 9330 3300 61 3 9310 5655 sales automaticheating com au Telephone Facsimile Emai...

Отзывы: