Flex 620
Installation - Revision 5, 11/22/01
___________________________________________________________________________________________
45
Building Control Module
BC-4 (30871)
Terminal #
Designation
Description
1
1 ON
CCT 1 relay N/O contact - remove the W2 B Jumper
2
1 COM
Common for CCT1 relays (terminals 1 & 3)
3
1 OFF
CCT 1 relay N/C contact - remove the W3 A Jumper
4
1 MON
Monitor point for CCT1 (requires 3.9K resistor to (-)
when used)
5
2 ON
CCT 2 relay N/O contact - remove the W6 B Jumper
6
2 COM
Common for CCT2 relays (terminals 5 & 7)
7
2 OFF
CCT 2 relay N/C contact - remove the W7 A Jumper
8
2 MON
Monitor point for CCT2 (requires 3.9K resistor to (-)
when used)
9
3 ON
CCT 3 relay N/O contact - remove the W10 B Jumper
10
3 COM
Common for CCT 3 relays (terminals 9 & 11)
11
3 OFF
CCT 3 relay N/C contact - remove the W11 A Jumper
12
3 MON
Monitor point for CCT 3 (requires 3.9K resistor to (-)
when used)
13
4 ON
CCT 4 relay N/O contact - remove the W14 B Jumper
14
4 COM
Common for CCT 4 relays (terminals 13 & 15)
15
4 OFF
CCT 4 relay N/C contact - remove the W15 A Jumper
16
4 MON
Monitor point for CCT 4 (use 3.9K to (-) when req.)
BC-4E (30872)
Terminal #
Designation
Description
1
5 ON
CCT 5 relay N/O contact - remove the W2 B Jumper
2
5 COM
Common for CCT 5 relays (terminals 1 & 3)
3
5 OFF
CCT 5 relay N/C contact - remove the W3 A Jumper
4
5 MON
Monitor point for CCT 5 (requires 3.9K resistor to (-)
when used)
5
6 ON
CCT 6 relay N/O contact - remove the W6 B Jumper
6
6 COM
Common for CCT6 relays (terminals 5 & 7)
7
6 OFF
CCT 6 relay N/C contact - remove the W7 A Jumper
8
6 MON
Monitor point for CCT6 (requires 3.9K resistor to (-)
when used)
9
7 ON
CCT 7 relay N/O contact - remove the W10 B Jumper
10
7 COM
Common for CCT 7 relays (terminals 9 & 11)
11
7 OFF
CCT 7 relay N/C contact - remove the W11 A Jumper
12
7 MON
Monitor point for CCT 7 (requires 3.9K resistor to (-)
when used)
13
8 ON
CCT 8 relay N/O contact - remove the W14 B Jumper
14
8 COM
Common for CCT 8 relays (terminals 13 & 15)
15
8 OFF
CCT 8 relay N/C contact - remove the W15 A Jumper
16
8 MON
Monitor point for CCT 8 (use 3.9K to (-) when req.)
Technical Manuals Online! - http://www.tech-man.com
Содержание FLEXALARM 620
Страница 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 7: ...Technical Manuals Online http www tech man com...
Страница 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 12: ...Technical Manuals Online http www tech man com...
Страница 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 20: ...Technical Manuals Online http www tech man com...
Страница 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Страница 34: ...Technical Manuals Online http www tech man com...
Страница 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Страница 64: ...Technical Manuals Online http www tech man com...
Страница 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...