background image

 

 

Flex 620

 

Installation  - Revision 5, 11/22/01

 

___________________________________________________________________________________________ 

 

35 

 

Bus Driver 
Module 

 

The bus driver module contains the circuitry that interfaces with the CPU module 
and the system modules.  The bus driver module is equipped with two Style Y or 
Z, limited energy signaling circuits and a city tie circuit. 
 

 

 

The bus driver module provides the system with the following : 

 

Controls default alarm bus if the CPU fails 

 

Monitors system modules for placement 

 

Monitors system for ground faults  

 Watchdog 

circuit 

 

Programmable Signal Circuits (1 & 2) 

 

Auxiliary Power Outputs (A+/A-, S+/S-, +/- 12VDC) 

 

 

 

The internal circuitry draws about 18mA from the +24V power supply with both 
signal circuits terminated with a 3.9K ohm resistor (with no current draw on the 
city tie circuit).  Each relay on the bus driver module draws 22mA when activated.  
In normal operation only the trouble relay is energized. 
 

City Tie 
Programming 

 

The bus driver module contains three jumpers for city tie programming (J1, J2, & 
J3)  located in the center of the board.  These three jumpers are used to select the 
reverse polarity or the master box option for the city tie connection. 

 

City Tie Programming - 
Set jumpers as follows: 

 
J1 

 
J2 

 
J3 

Reverse Polarity 

 

Master Box 

 

 

X  =  jumper installed 

 

Installation 
Diagram 

 

Refer to drawings  D-W1142, Wiring  Minimum System Flex 620 and C-W847, 
Bus Driver Module. 

 

 Cable Connections 

 

P1 Connector  

Interconnect  (ribbon cable) to IBX1 on the  CPU module  

J5 Connector  

Interconnect  (ribbon cable) to Left I/O modules 

J6 Connector  

Interconnect  (ribbon cable) to Left Display modules 

J7 Connector  

Interconnect  (ribbon cable) to Right Display modules  

J8  Connector  

Interconnect  (ribbon cable) to Right I/O modules 

J9 Connector 

Interconnect (ribbon Cable) to Cabinet Expander 

J11 Connector 

Interconnect  (ribbon cable) to P1 on the common control display 

J12 Connector 

Cable connector  to J2 - Power Supply  

J13 Connector  

Cable connector  to P3 - CPU module 

J16 connector 

Three conductor cable  to J3 power supply  

J17 Connector 

Interconnect  (ribbon cable) to  J2  on the  Relay Expander Card 

 

Technical Manuals Online! - http://www.tech-man.com

Содержание FLEXALARM 620

Страница 1: ...NTIONAL FIRE ALARM CONTROL PANEL Installation Operation Manual The Gamewell Company P N 71217 60 Pleasant Street Revision 5 Ashland MA 01721 11 22 01 UL FM CSFM MEA Listed Technical Manuals Online htt...

Страница 2: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 3: ...Gamewell Company Such information and technical drawings may not be copied or reproduced in any manner or disclosed to organizations that might be competitive to Gamewell without the express prior wri...

Страница 4: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 5: ...rol panels to verify compatibility To maximize system performance and minimize risk of damage to the equipment we suggest using all Gamewell Components 4 There is no substitute for proper maintenance...

Страница 6: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 7: ...Technical Manuals Online http www tech man com...

Страница 8: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 9: ...Condition 17 default 17 Alarm Condition default 18 OPERATING PROCEDURES 19 INSTALLATION 24 Flex 620 System Housing 25 Hardware Assembly 26 Module Identification and Placement 28 Main Power Supply 30...

Страница 10: ...rol By Event 59 Access Levels 60 Figure 4 1 Common Control Display Operating Mode 60 Password Entry 60 Input Circuit Programming 63 Output Circuit Programming 64 Restoring Output Circuits 65 Programmi...

Страница 11: ...81 Change Dictionary 81 Change Dict Words 82 Upload Dictionary 82 Dictionary File 83 Change Card 84 Change Misc 84 Change Menu 1 85 Change Pass 85 Change Code 86 Change Date 87 Change Seq 87 Change B...

Страница 12: ...Technical Manuals Online http www tech man com...

Страница 13: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 14: ...Flex 620 System Description Revision 5 11 22 01 2 Section 1 FLEXALARM 620 System Description System Overview Technical Manuals Online http www tech man com...

Страница 15: ...c system configuration in memory Then a control by event table is automatically created that allows any system input to activate the system outputs Upon completion of the initialization process the sy...

Страница 16: ...ing functions and system memory as well as providing the local remote communications interface Relay Expansion Module The Relay Expansion Module REM provides 4 common relay circuits When connected to...

Страница 17: ...ower left hand corner of the cabinet and connects via interconnecting cables to the bus driver module Lead Acid Battery Charger The lead acid battery charger module is provided with the main power sup...

Страница 18: ..._________ Indicating Module Universal Signal Module The Flex 600 series universal signal modules USM 4 USM 8 are a multi function output modules available in either 4 or 8 circuit increments These mod...

Страница 19: ...ol module is available in 4 or 8 circuit modules that are monitored and controlled by the MPU bus Their relays are rated at 10 Amps with supervised feedback points for positive confirmation of the pro...

Страница 20: ...Technical Manuals Online http www tech man com...

Страница 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...

Страница 22: ...gnal silence switch is alternating action switch Pressing the signal silence switch will return the silenced circuits to an active state Drill The Drill tactile switch DRILL will activate all circuits...

Страница 23: ...tion When pulsing this indicates a problem with the incoming AC line voltage main or backup power supplies BATTERY FAULT The yellow Battery Fault LED indicates a problem with the battery or battery co...

Страница 24: ...trouble has been acknowledged SIGNAL SILENCE The yellow Signal Silence LED indicates the audible signals connected to the system are not sounding SIGNAL SILENCE SOUNDING The yellow Signal Silence LED...

Страница 25: ...bottom Relays 5 through 8 are fixed on the right side of the display top to bottom The display is complete with eight tactile switches eight red LED s and eight green LED s The eight point tactile swi...

Страница 26: ...guished the system internal buzzer is silent all switches are inactive with the exception of the Enter button and all indicating devices are inactive __________________________________________________...

Страница 27: ...ice s has been cleared and the momentary reset switch has been depressed If no further supervisory alarms exist in the system the panel will return to normal quiescent condition otherwise the panel wi...

Страница 28: ...smoke detector go into alarm on the same AND circuit a second alarm output will occur This circuit is useful for a simple cross zone of two detectors An example of typical application would be in an e...

Страница 29: ...y tie and common alarm relays activated ___________________________________________________________________________________________ Normal Quiescent Condition default When the system is in the normal...

Страница 30: ...ts have been energized B If there are additional signal circuits in the system each circuit s red Alarm LED will be On steady to indicate that the circuit has been energized 5 Building Control Relay C...

Страница 31: ...driver module display acknowledge ACK switch will stop pulsing and extinguish Any outputs programmed to return to the normal condition upon pressing the ACK switch will return to normal at this time...

Страница 32: ...dition the momentary Reset switch should be depressed When the user presses the RESET switch the following actions will occur 1 All signal circuits will deactivate 2 All output relays circuits program...

Страница 33: ...ng control circuit to Bypass will disable the circuit from activating E City Tie s bypassed Programming any City Tie circuit to Bypass will disable the circuit from the transmitting alarm WALKTEST Pro...

Страница 34: ...Technical Manuals Online http www tech man com...

Страница 35: ...This page intentionally blank Technical Manuals Online http www tech man com...

Страница 36: ...m Operation Revision 5 11 22 01 _______________________________________________________________________________________________ 24 Section 3 FlexAlarm 620 Installation Technical Manuals Online http ww...

Страница 37: ...ring terminals which the modules plug into are mounted directly to the backbox for ease of installation and servicing Modules can be removed for servicing without disturbing field wiring Systems are a...

Страница 38: ...ing shipment Notify the manufacturer immediately if damage is detected Flex 620 Control Panel Mounting Complete the following instructions to mount the Flex 620 control panel The instructions are appl...

Страница 39: ...initiating indicating building control module etc into alignment pins of cross rails 8 Connect the following interconnecting cables ribbon and power cables Reference drawing D W1142 all applicable wi...

Страница 40: ...sent in the common control section operating display signal circuits city tie etc Cards 8 39 Card locations 8 through 39 are the optional modules installed in the cabinet bays see Figure I 1 Each modu...

Страница 41: ...10 Ckt 33 40 jumper to 3 18 Ckt 41 48 jumper to 3 22 jumper to 3 15 jumper to 4 11 Ckt 49 56 jumper to 4 19 Ckt 57 64 jumper to 4 23 jumper to 4 FLEX 620 Expansion Cabinets w Bus Extender D I S P L A...

Страница 42: ...pplicable refer to C W857 Aux Power Supply ___________________________________________________________________________________________ Specifications Input Voltage 120 VAC 50 60 Hz 3 amps Max Optional...

Страница 43: ...ignation Description OUTPUT J1 connector RED 24VDC auxiliary power 4 amps available for signal circuits J1 connector BLK 24VDC auxiliary power 4 amps available for signal circuits J1 connector WHT Mon...

Страница 44: ...21 VDC Common Smoke Detector Power 3 S 21 VDC 125mA resetable regulated power 4 second reset time 4 S 21 VDC common Security Power 5 12 12VDC 2 Amps regulated power 6 12 common for 12VDC City Tie 7 M1...

Страница 45: ...ized A feedback circuit must have less than 50 ohms in loop resistance The function of relays K1 K4 Relay K1 Common Alarm Relay K2 Common Trouble Relay is normally energized Relay K3 Common Supervisor...

Страница 46: ...or 220 VAC resistive fused 10 amps 8 2 M Trouble relay feedback point to monitor status of controlled device RELAY 3 COMMON SUPERVISORY Terminal Designation Description 9 3 NO Normally open Superviso...

Страница 47: ...r module contains three jumpers for city tie programming J1 J2 J3 located in the center of the board These three jumpers are used to select the reverse polarity or the master box option for the city t...

Страница 48: ...rd To install the U18 IC must be removed from its socket and replaced with the interconnecting cable from the Isolated RS 232 Card SW1 Default Settings S1 Open Do Not Change S2 Open Do Not Change S3 A...

Страница 49: ...LED s and the internal sounder LED annunciation is also provided for AC power PreAlarm 2 signal circuits City Tie connection and Bypass Installation Diagram Refer to drawing D W1142 Wiring F620 Minim...

Страница 50: ...rough S1 4 The I O circuit module uses the lower terminal block and connects via cables to the bus driver module The conventional input module and its display require one bay of the F620 system Note W...

Страница 51: ...Initiating CCT 8 Class A Adapter Conventional Input Module Terminal Description Top Card 30869 CIM SDA Terminal Designation Description 1 1L1 Initiating CCT 1 Class A Return 2 1L2 Initiating CCT 1 Cl...

Страница 52: ...osition each The SIGNAL I O board has an option that allows programming of the signal circuits to be operable under Default Alarm Mode A DIP switch S2 is provided on the module to select which signali...

Страница 53: ...dicating CCT 8 output Class A Adapter Universal Signal Module Terminal Description Top Card 30940 USM SZA Terminal Designation Description 1 1AL1 Indicating CCT 1 output Class A return 2 1AL2 Indicati...

Страница 54: ...lay Expander Module The relay expander provides the addition of four 4 supplementary form C 10 amp fused relay contacts The module also provides four 4 feedback input points switched negative using 3...

Страница 55: ...15 4 C Form C common contact 10A 30VDC or 220VAC resistive fused 10A 16 4 M CCT 4 Relay feedback point to monitor status of controlled device Relay Expansion Module RM 4E 30874 Terminal Designator De...

Страница 56: ...e slot in the Module bus Building Control Expander The building control expander module provides an additional eight 8 form A B jumper programmable 10 amp relays set up in four 4 ON relays and four 4...

Страница 57: ...COM Common for CCT 4 relays terminals 13 15 15 4 OFF CCT 4 relay N C contact remove the W15 A Jumper 16 4 MON Monitor point for CCT 4 use 3 9K to when req BC 4E 30872 Terminal Designation Description...

Страница 58: ...in the Module bus Display Module The display module provides eight 8 red circuit alarm LED s eight 8 yellow circuit trouble LED s Eight 8 circuit tactile switches are provided for programming and Byp...

Страница 59: ...uring the power up sequence 6 System is at idle the normal quiescent condition The Power On is illuminated ___________________________________________________________________________________________ S...

Страница 60: ...4 STANDARD BASE SMOKE 70884 70885 70886 HD 3 25 70892 HB 13 STANDARD BASE W RELAY SMOKE 70884 70885 70886 HD 3 25 70893 STANDARD BASE HEAT DETECTOR 70887 70888 70889 70890 MAX AL CURRENT 100 MA 70894...

Страница 61: ...71582 CH CF1 IS 24 CFW Chime SS Vib White 245 71303 CH DF1 IS 24 VFR Chime SS Vib Red 245 71548 SM 12 24 R Single Circuit Sync Module 025 71549 DSM 12 24 R Dual or Class A Sync Module 038 70871 MIZ 2...

Страница 62: ...Strobe 15 Cd Sync 096 71569 RSP 241575 VFR Strobe 15 75 Cd Plate Mount 100 71554 SRP 241575 VFR Strobe 15 75 Cd Plate Mount Sync 138 71555 SR 241575 VFR Strobe 15 75 Cd Sync 138 71557 RSP 2430 VFR St...

Страница 63: ...10 AWG OHM 1000 0 5amp 1 0amp 1 5amp 2 0am p 18 6 5 400 200 130 100 16 4 1 620 300 210 160 14 2 6 1000 500 330 250 12 1 6 1600 800 520 400 10 1 0 2500 1250 840 620 CIRCUIT CHARACTERISTICS CIRCUIT EOL...

Страница 64: ...Technical Manuals Online http www tech man com...

Страница 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...

Страница 66: ...rogramming mode Selecting Options 1 Each labeled key function switch on the CCD has an Upper and a Lower LED associated with it To choose a particular option press the tactile key switch which is asso...

Страница 67: ...within the specified time limit the first alarm is ignored 3 AND The AND Fire Initiating Circuit will operate as an Automatic Alarm Initiating Circuit for the first two wire smoke detector alarm repo...

Страница 68: ...cle C MARCHTIME 120 Marchtime 120 circuits when activated will provide a 24 VDC output on the selected circuits at a 120 pulses per minute rate with a duration of 50 on and 50 off cycle D TEMPORAL Tem...

Страница 69: ...for steady or pulsing DC marchtime temporal etc and programmed separately 2 Signal Circuit types being selected on a USM Module are always allocated in circuit pairs an upper lower pair Each signal c...

Страница 70: ...larm C Drillable Any signal circuit programmed as drillable will activate when the drill feature is activated Restoring Outputs A Restore On ACKNOWLEDGE Any active output point programmed to restore o...

Страница 71: ...m level System Default activates ALL output signal circuits during a level 1 alarm C Relay Circuits Activation Any combination of relay circuit s may be assigned to activate from an input group When a...

Страница 72: ...to programming Programming can only be completed using the level 4 password entry Default password for level 4 is 4444 When this mode is entered the key switches are redefined Reversing the front disp...

Страница 73: ...d is entered This indicates that a new access level has been accepted B Password Required If a function is attempted from a level that does not allow access to that function i e Bypass from level 2 th...

Страница 74: ...ption has been selected press the ENTER key The Password Required and Password Accepted LEDs will flash twice indicating that your selection has been accepted Note If a key that is not available for s...

Страница 75: ...ble for input circuit types Automatic Verified And Supervisory Acknowledge Reset Signal Silence Drill B Once the desired circuit type LED is illuminated press the ENTER key to select the indicated cho...

Страница 76: ...itch Note To deselect a circuit press the associated circuit switch until the LED is extinguished Any circuit deselected will default to a steady signal and all control by event information will be re...

Страница 77: ...cuits LED s should be Lit in the default configuration then deselect the desired circuit s This will cause the LED to extinguish When the circuit LED is not lit for both the Signal Silence and Acknowl...

Страница 78: ...t 1 From the programming mode select the Auto Silence option and press the ENTER key 2 Select all of the Signal Circuits that should automatically silence by pressing their associated circuit key 3 Af...

Страница 79: ...by pressing the associated circuit key Once the desired group has been selected indicated by their associated LED s on press the ENTER key to confirm the selection Note If any previously programmed o...

Страница 80: ...communication packages for computers will allow you to set the proper protocol for the communications port of your computer Procomm Software Configuration When using PROCOMM to communicate with your F...

Страница 81: ...p From the ProComm SETUP MENU select option 4 to display the GENERAL SETUP menu The following settings should be displayed 1 Editor name 2 Default d l path 3 Default log file PROCOMM LOG 4 Screen dump...

Страница 82: ...troubleshooting by providing detailed information of system faults Access Levels System access levels may be accessed via the computer By transmitting a Carriage Return Enter to the system you will be...

Страница 83: ...Menu The System Menu menu is displayed when the programming password is entered System Menu 1 Display 2 Change 3 Test 0 Exit Display Menu Selecting the Display option from the System Menu allows the...

Страница 84: ...rd 1 ID 12 is CCM1 LEDs T Switches Card 2 ID FF is Vacant Card 3 ID FF is Vacant Card 4 ID 01 is CCM4 2 Sig Ckt Class A Card 5 ID 02 is CCM5 4 Rel Ckt Card 6 ID 05 is CCM6 Misc Ckts Card 7 ID 07 is CC...

Страница 85: ...9 Card numbered 8 through 39 are individual modules physically installed in cabinet bays 4 8 bay cabinets and 4 8 bay expander cabinets see Installation Section 3 Figure 3 1 for cabinet layout Each mo...

Страница 86: ...w no tactile sw Left Control Display 16 Combo Red Green Yellow LEDs no 3 pos sw tactile sw installed Left Control Display 13 Combo Red Yellow LEDs no 3 pos sw no tactile sw Right Control Display 12 Co...

Страница 87: ...ftware packages follow the procedure required for that software to receive an ASCII file The next CR the system receives will start the transmission of the file Configuration Menu 1 Display 2 Download...

Страница 88: ...smit the complete set of 5 dictionaries to the RS 232 port When this is selected the system prompts the user to perform several steps These steps are the actions required to receive an ASCII file when...

Страница 89: ...ding the system status changes for the previous 1000 events or since the last time the system Smart Start feature was invoked Display Menu 1 Config 2 Dict 3 Events 4 Misc 0 Exit 3 Start of Event Buffe...

Страница 90: ...Display Menu 1 Config 2 Dict 3 Event 4 Misc 0 Exit 4 Display Menu Misc 1 Pass 2 Codes 3 Ver 4 Zone 0 Exit 1 1 Pass 1111 User ID USER1 Sec 1 2 Pass 2222 User ID USER2 Sec 2 3 Pass 3333 User ID USER3 S...

Страница 91: ...3456 35 123456 36 123456 37 123456 38 123456 39 123456 40 123456 41 123456 42 123456 43 123456 44 123456 45 123456 46 123456 47 123456 48 123456 49 123456 50 123456 51 123456 52 123456 53 123456 54 12...

Страница 92: ...one cards installed in the system The card ID and description is displayed along with each associated circuit type and assigned code information Display Menu Misc 1 Pass 2 Codes 3 Ver 4 Zone 0 Exit 4...

Страница 93: ...he PROCOMM software package to Upload an ASCII file When using other software packages the keystrokes required to Upload an ASCII file should be followed When using the PROCOMM software package the fo...

Страница 94: ...ry a file containing the new dictionary entries must be created using an ASCII text editor The SAN RAN disk P N XXXXX contains the AHED text editor that may be used to create the dictionary file The d...

Страница 95: ...throughout the five dictionaries The end of dictionary five is also signified by two fore slashes Some important points to keep in mind when writing the file are as follows Dictionary one through dict...

Страница 96: ...ll ensure that the control by event table is Change Menu 1 Config 2 Dict 3 Card 4 Misc 0 Exit 3 Change Card Menu 1 Add 2 Delete 0 Exit 1 Enter Card To Add Delete Existing Card First Press Enter Key To...

Страница 97: ...ssigned to that password is defined NOTE Before changing the password 4 programming password make sure that you have added a new password to access the programming Sec 4 area Change Menu Misc 1 Menu1...

Страница 98: ...ou to change the Timing the number of Cycles and the output of the signal circuits after the code is complete silence or March Time signal Change Menu 1 1 Pass 2 Code 3 Date 4 Seq 5 Baud 6 Words 0 Exi...

Страница 99: ...tion allows the user to redefine the access levels associated with each of the sequence keys Each of these keys is assigned an access level by default The Acknowledge key is assigned to level 1 access...

Страница 100: ...nopqrstuvwxyz 0123456789 ABCDEFGHIJKLMNOPQRSTUV WXYZ _ abcdefghijklmnopqrstuvwxyz 0123456789 ABCDEFGHIJKLMNOPQRSTUVWXYZ _ abcdefghijklmnopqr stuvwxyz 0123456789 ABCDEFGHIJKLMNOP QRSTUVWXYZ _ abcdefghi...

Страница 101: ...5 Baud 6 Words 0 Exit 6 Press an I O Ckt or Enter Ckt 01 Press an I O Ckt or Enter Ckt 49 Enter Ckt s Word To Change 1 5 1 Current Word Enter Replacement Word 0 127 1 Fire Alarm Enter Ckt s Word To Ch...

Страница 102: ...y until a2 is displayed a3 should be displayed if the third letter is desired and should be displayed if the number associated with that key is desired 1 2 The case of the letters may be changed by pr...

Страница 103: ...u Misc 1 Menu1 2 Menu2 0 Exit Change Menu 2 1 City 2 Sig Sil 3 Ann 4 Trbl 5 Dialer 6 Prefix 0 Exit 1 Press Enter Key To Exit Press Any Other Key To Toggle City Tie Is In Standard Mode City Tie Is In C...

Страница 104: ...Installed is selected Normal reporting of AC failure troubles is restored when the Dialer Is Not Installed option is selected Change Menu 2 1 City 2 Sig Sil 3 Ann 4 Trbl 5 Dialer 6 Prefix 0 Exit 5 Pre...

Страница 105: ...put of the card location number see installation section for card location numbers to be tested The card is continuously scanned and a real time value in Hexadecimal format base 16 is returned for eac...

Страница 106: ...te when the display switch is pressed NOTE When card 0 main display is selected on the 630 and 650 systems no input card option is displayed Pressing the front panel switches will toggle the LED s and...

Страница 107: ...wo measurements must be greater than 142 but less than 255 for a reading of Good Note The values displayed are derived from an A D conversion and not displayed in actual voltages Test Menu 1 Input 2 O...

Страница 108: ...feedback point and 006 for each active Normal 022 per active circuit BC 8 010 003 for each inactive feedback point and 006 for each active Normal 022 per active circuit CABINET EXPANDER 001 001 ALARM...

Отзывы: