14
5-3
Select External Wall Mounted W40/50E & W50/80E
5-3.1 Service Access
External Wall Mounted Boilers have a large hinged front door that gives access to the
Control Panel and enables all routine servicing to be carried out without the necessity of
removing main case or flue. The door can be lifted off in windy conditions.
A large bolted service door is provided on the front of the heat exchanger giving easy
access to the baffles and combustion chamber.
5-3.2 Heating Connection
The flow and return connections are on the top of the Boiler heat exchanger - 1” female
BSP. The standard arrangement is to connect through the back panel as shown in fig.
5-3b.
5-3.3 Boiler at Ground Level
The External Wall Mounted range can be wall mounted at ground level, however the
following conditions must be considered.
1.
A terminal guard must be fitted (not supplied).
2.
A 50mm free air space must be provided under the Boiler.
3.
The Burner is supplied for two pipe operation and will probably require changing to
single pipe operation.
4.
Protection against rodent intrusion is essential.
SERVICE DOOR
W40/80E SHOWN
Fig. 5-3a Service Access
INST
INST
INST
INST
INSTALLA
ALLA
ALLA
ALLA
ALLATION 5
TION 5
TION 5
TION 5
TION 5
5-2.5 Oil Connections
All Wall Mounted Boilers are supplied with a pump set for two pipe oil system.
FIRE VALVE SENSOR
FIXED ABOVE BURNER
OIL HOSES
✓
FLOW
ALTERNATIVE BOTTOM ENTRY
NO VALVES IN
RETURN LINE
FIRE VALVE
RETURN
FLOW
SHUT OFF VALVE
FILTER
✓
✓
SUPPLIED WITH BOILER, SEE SECTION 13.
Fig. 5-2f Recommended Two Pipe Oil Connection - Wall Mounted Internal
✓
✓
205
35
45
1 BSP/F
25 min
150 max
F
R
Fig. 5-3b Heating Connections