29
Governors America Corp. © 2021 Copyright All Rights Reserved
EEG7500 Enhanced Electric Governor 8-2021-A8 PIB5115
PoSITIon conTroL TUnInG
SeTTInG
oPTIonS
DefaULT
noTeS
Position Mode
Position 1
Position 2
Position 3
0 - 100
0
Position % change for fixed position control settings.
Variable Position Start
Variable Position End
0 to 100 %
Start - 0
End - 50
Start (End) position for the variable position
Variable Position Input Minimum
Variable Position Input Maximum
0 to 75 %
Variable position input position indicating where variable position control
starts (ends).
Calibrate Minimum
Calibrate Maximum
Button
NA
Automatic calculation tool sets the variable position input minimum or maxi
-
mum position based on the current value.
Variable Position Input Position
0 to 100 %
0
Current location of the variable position input control.
Position Trim Increase Rate,
Position Trim Decrease Rate
1 to 100 %/s
1
Rate of increase (decrease) when using the trim increment input.
Position Offset
0 to 100 %
0
Current position offset (position trim) added to the position request.
Active Position Sensor
Primary,
Redundant
Redundant
The current actuator position as determined by the feedback sensor input
Position Feedback Low
Position Feedback High
Range:
0 to 5 V DC
Low - 1
High - 4
The voltage signifying the upper (open) position of the actuator. Must be 0.5
V DC apart from Low.
Redundant Position Feedback
Checkbox
Checked
Enables / Disables the redundant feedback sensor monitoring. Requires the
sensor to be routed through the IO routing.
Redundant Feedback Low
Redundant Feedback High
0 to 100 %
Low - 0
High - 100
Position of the redundant feedback sensor input representing the actuator
closed (open) position. High and low must be 10 % apart.
Redundant Position
0 to 100 %
0
Reports back calculated actuator position based on the redundant feedback
sensor input.
Feedback Auto-Calibrate
Button select
NA
Enables and starts the automatic limit calibrations. Valid for FSC and PM
modes only.
Position PID Tuning
Position Gain (P)
1 - 100
50
Gain of the position loop when in uniform gain mode.
Positions Stability (I)
1 - 100
50
Stability/Integrator of the position loop when in uniform gain mode
Auto-Tune
Button select
NA
Enables and starts the automatic PID calibrations. Valid for FSC and PM
modes only.
enable Position control Table
GAC
onfig
TOOl - SETTING All VAlUES (CONTINUED)
19