I/O Configuration:
Each hardware input source is mapped to ONE data parameter.
SeTTInG
oPTIonS
DefaULT
noTeS
AI 1
0 - 5 V DC,
4 - 20 mA
0 - 5 V DC
Sets the variable speed input (AI1) to 0 - 5 V DC /Resistive mode of 4 - 20 mA mode
for Connector: 2 Pin: 7
AI 2
±3 V DC,
0 - 10 V DC
0 - 10 V DC
Sets AI2 to
± 3 V DC Mode for Connector: 2 Pin: 8.
AI 3
4 - 20 mA
4 - 20 mA
AI 4
0 - 5 V DC,
4 - 20 mA
0 - 5 V DC
Sets the variable speed input (AI4) to 0 - 5 V DC/Resistive mode or 4 - 20 mA mode
for Connector: 2 Pin: 10.
Run/Stop Input
Disabled
Controls the actuator output and is used to put the system into standby state. Set
to Override and ON to enable the STOP button operation.
From the Physical Input
mapping box on the I/O Configuration tab, set the Run/Stop Input signal to On from
the GAConfig Tool.
Speed Select A
Speed Select B
Digital Input 1
Digital Input 2
Configures the input data signal routing for the current operating mode. Values may
either be a fixed analog, fixed discrete, or mapped to a hardware input source. Each
source may only be mapped to ONE data element. NFC and NFSC mode
Variable Speed Input
Analog Input 1
Sets the variable speed input (AI4) to 0 - 5 V DC /Resistive mode or 4 - 20 mA
mode for Connector: 2 Pin: 10.
Auxiliary Input
Analog Input 2
Controls the engine synchronization and load sharing operation. NFC and NFSC
mode
Speed Trim Input
Override
Sets the amount of speed trim used during fixed speed operation. Settings are
adjustable to +/- 10 % of requested fixed speed. NFC and NFSC mode
Speed Increment Input
Speed Decrement Input
Override
Disabled
Used to increase or decrease the current speed by a specified rpm, per seconds
held in a specific state of a discrete input. This change ends when position source is
switched or EEG is re-powered on. Only one function is needed, both do not have
to be set. NFC and NFSC mode
Position A Input
Position B Input
Override
Disabled
Configures the input data signal routing for the operating mode. Values are either
fixed analog, fixed discrete, or mapped to a hardware input source. Each hardware
input source may only be mapped to ONE data element.
Redundant Feedback Input
Override
Disabled
Setting this parameter allows the use of another analog input as a redundant feed-
back position input. It can be set to a different range and polarity from the active
position sensor.
Variable Position Input
Override
Disabled
Determines the position request during variable speed positioning. Configure for
high and low input, position, and gain. The value of the configured position and gain
values are interpolated based on the value of the variable position input. NFC and
NFSC mode
Position Increment Input
Position Decrement Input
Override
Disabled
Sets a temporary % decrease or increase in the current position for a specified
number of seconds. This change ends when position source is switched or EEG is
re-powered. Only one parameter is needed, both do not have to be set.
SSW1, SSW2, SSW3 Limit
100 to 6000
1800
Speed limit (rpm) for the speed switch 1, 2, or 3 output. MAX speed is limited by a
converted speed of 12 kHz.
SSW1, SSW2, SSW3 Latch
On - Off
On
Controls speed switch 1, 2, 3 latching function
PSW1, PSW2, PSW3 Limit
0 - 100 %
1-00
Position limit for the position switch 1 output
PSW1, PSW2, PSW3 Latch
On - Off
On
Controls Position switch 1, 2, or 3 latching function.
DO 1
Normally Open,
Normally Closed
Normally Open
Selects the default state for Connector: 3 Pin: 16.
DO 2
Normally Open,
Normally Closed
Normally Open
Selects the default state for Connector: 3 Pin: 17.
DO 3
Normally Open,
Normally Closed
Normally Open
Selects the default state for Connector: 3 Pin: 18.
Digital Output 1 Source
Digital Output 2 Source
Digital Output 3 Source
Selection list
Speed Switch 1
Alarm
Warning
Configures the data source for output 1, 2, or 3. Output data elements may be rout
-
ed to multiple hardware outputs.
Analog Output 1 Source
Engine Load
GAC
onfig
TOOl - SETTING All VAlUES (CONTINUED)