AC
INPUT
/
OUTPUT POWER CONNECTION
In order to choose the cable section for each ups, refer to the chapter in the user manual entitled “Cables section”.
Connect the power cables L1, L2, L3 and N to the input terminals L1, L2, L3 and N of each UPS.
Connect the load cables L1, L2, L3 and N to the output terminals L1, L2, L3 and N of each UPS.
Example of parallel connection of three units
When connecting power to UPSs the instructions below
must
be followed to ensure a good load share when operating from
bypass:
Supply cable lengths must be equal: a1 = a2 = a3.
Output cable lengths must be equal: c1 = c2 = c3.
a1, a2, a3, c1, c2, c3 must have a minimum length
greater than 3m.
MAGNETO-THERMAL SWITCHES:
To prevent a system failure from impacting on all of the machines present, it is essential that the input of each UPS be protected
by a completely independent magneto-thermal switch which is installed upstream of the machine (for rating of the switches, see
the indications of the UPS manual in the section “PROTECTION DEVICES”).
DIFFERENTIAL SWITCH:
To avoid false alarms, when there are various machines in parallel, one single differential switch upstream of the entire system
must be inserted as indicated in figure B.
Fig. A
Fig. B
Input terminal boards
IN
Output terminal boards
OUT
Input cables lenght
a1, a2, a3
Output cables lenght
c1, c2, c3